Design of the Shield Contact Element
The shield contact element consists of the following parts:
• a clamp with 2 screwed bolts for fixing to the rail
(order no.: 6ES7390-5AA00-0AA0) as well as
• The shield terminals
Depending on the cable cross-sections used, you must use the following shield terminal:
Table 5- 5
Cable and shield diameter
2 lines with in each case 2 to 6 mm shield diameter
1 line with 3 to 8 mm shield diameter
1 line with 4 to 13 mm shield diameter
Bus cable
The shield contact element is 80 mm wide with space for two rows each with 4 shield
terminals.
Installing the Shield Contact Element
Install the shield contact element as follows:
1. Push the two bolts of the fixing bracket into the guide on the underside of the rail. Position
the fixing bracket under the modules to be wired.
2. Bolt the fixing bracket tight to the rail.
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Assignment of cable cross-sections and terminal elements
5.4 Wiring the power supply and modules
Shield connection terminal
order no.:
6ES7390-5AB00-0AA0
6ES7390-5BA00-0AA0
6ES7390-5CA00-0AA0
Connecting
85