Siemens SIMATIC ET 200M Operating Instructions Manual page 15

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

"SIMATIC S7-DP-Slave"
The ET 200M distributed I/O system is a constituent part of the SIMATIC S7 automation
system.
In other words, STEP 7 provides support when configuring, assigning parameters to and
programming the ET 200M in the DP master system as well as for the commissioning and
diagnostics. Special services and functions of the IM 153-2 (e.g. configurable FM) can be used
to their full extent only in the SIMATIC S7 / PCS 7.
If you use the ET 200M on a DP standard master (e.g. S5-95U), the configuration tool will also
provide support with the GSD file, but, for example, you must pay attention to the technical
data (project data) of the DP master (possible parameter assignment and diagnostics
message frame lengths etc.).
The PROFIBUS standard IEC 61784-1:2002 Ed1 CP 3/1 also includes the DPV1-mode. You can
use this mode only if you integrated the GSD-file Revision ≥ 3.
The GSD-file Revision 2 remains available and hence the compatibility with earlier versions of
the IM 153-x is assured.
Components
A series of components are provided for the configuration and commissioning of the ET
200M. The most important components and their functions are listed in the following table:
Table 1- 1
ET 200M components
Components
Mounting rail
Accessories:
Shield connecting element
Mounting Rail for Active Bus Module
Accessories:
Shield connecting element
active bus modules
Active bus modules (BM)
BM IM/IM for redundancy with 2 IM 153-2
BM IM/IM for redundancy with 2 IM 153-2Bx00
BM PS/IM for PS 307; 2 A and IM 153-x
BM 2 40 for two 40 mm wide S7-300 modules
BM 1 80 for one 80 mm wide S7-300 module
Accessories
Explosion-proof partition
Backplane bus and bus module cover
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Function
... is the rack for the ET 200M.
... is the special rack for the ET 200M for
the functions "Module change during
operation", "Redundancy" and IM 153-4
PN.
... provide the S7-300 backplane bus. In
other words, if a module is missing, all
1
the other modules can still be reached via
the backplane bus.
1
Product overview
1.4 ET 200M distributed I/O device
Diagram
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents