Maintenance and service
7.11 Saving data and updating the IM 153-4 PN
Example configuration
Update from PD / PC via PROFINET IO (direct)
The PG / PC with the update files is directly connected to the PROFINET interface of the
IM 153-4 PN (refer to the following figure).
Note
If no STEP 7 project containing the respective IM 153-4 PN is available, the update can also
take place via the online view (available nodes) in STEP 7.
Figure 7-7
Update via SIMATIC Micro Memory Card
The following SIMATIC Micro Memory Cards are available for the update:
Table 7- 4
Type
SIMATIC Micro Memory Card 2M
SIMATIC Micro Memory Card 4M
SIMATIC Micro Memory Card 8M
To perform an update via SIMATIC Micro Memory Card, proceed as follows:
1. Use STEP 7 and your programming device to transfer the update files to a SIMATIC Micro
Memory Card. The data saved on the SIMATIC Micro Memory Card is then overwritten by the
update files.
2. Switch off the voltage to the IM 153-4 PN.
3. Remove the existing SIMATIC Micro Memory Card containing the device name from the
module slot.
To eject the SIMATIC Micro Memory Card, push in the ejector in the lower section of the
module slot with a small screwdriver or ball-point pen.
126
Update via PROFINET IO (PG / PC directly on IM 153-4 PN)
Available SIMATIC Micro Memory Cards for an update of the IM 153-4 PN
Order numbers
6ES7953-8LL20-0AA0
6ES7953-8LM20-0AA0
6ES7953-8LP20-0AA0
Operating Instructions, 04/2022, EWA-4NEB7806006-09