Interrupt, error and system messages
9.1 PROFIBUS DP
Table 9- 9
Error type of the channel-related diagnostic - manufacturer-specific
Error type
Error text
10000
16
Parameter con-
B
D
figuration error
10001
17
Encoder or load
B
D
voltage missing
10010
18
Fuse faulty
B
D
10011
19
Communication
B
D
error
10100
20
Ground error
B
D
10101
21
Reference
B
D
channel fault
10110
22
Hardware inter-
B
D
rupt lost
10111
23
Warning
B
D
11000
24
Switch off
B
D
11001
25
fail-safe switch
B
D
off
11010
26
External error
B
D
11011
27
Unclear error
B
D
11100
28
reserved
B
D
198
Meaning
Parameter configuration error, e.g.:
•
Module cannot evaluate the parameter (unknown, inad-
missible combination, ...)
•
Module not configured
•
User calibration does not correspond to the configuration
•
Calibration error
The following voltages could me missing:
•
external supply voltage
•
Voltage to operate the module
The user´s exchangeable fuse has failed
With F technology (PROFIsafe):
•
Error with the consecutive number (sign of life)
•
Error in the user data CRC
•
User data timeout
Ground error, e.g.:
•
The permissible common mode voltage for isolated
channels has been exceeded
•
The M line is broken in the case of isolated channels
Error on the reference channel
Hardware interrupt has become lost
There could be a warning, if limit values like:
•
Speed
•
Load current
are exceeded
There could be a switch off:
•
Power switch is triggered on account of short circuit,
asymmetry, contact to earth
•
Thermistor triggered
•
Quick stop
•
fail-safe switch off
Trigger / cause for fail-safe switch of is given
External (process-side) error, e.g.:
•
Sensor error
•
Actuator error
•
Sensor data is incorrect
Unclear errors are those that are not specified in any more
detail
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Remedy
Correction of the pa-
rameterization
Correction of the pro-
cess wiring
Replace the fuse
Check the communica-
tion paths
Correction of the pro-
cess wiring
Replace the reference
channel module
Correction tuning of
program /
process / module
Correction tuning of
program /
process / module
Remedy the cause of
switch off and
acknowledge
Remedy the cause of
switch off
Replace sensor /
actuator / correct pro-
cess wiring
different, depending
on cause of error
ET 200M