Message To Outputs A1 And A2 (Iq 330 & Iq 330M Base Module Only) - Eaton Cutler-Hammer IQ 300 Series Instructions For Installation, Operation And Maintenance

Table of Contents

Advertisement

default value chosen. This is all computed internally based on 3 Phase Voltage
readings. This value can not be viewed and will only be one of the four values listed.
Enter the PT Ratio two times every time you install the IQ
230. This will ensure proper default voltage and calculation
when your using the Voltage Trip feature.
Once the mode is selected for the two outputs The Trip
Value can be assigned. To change the Trip Value setting,
scroll up or down the Edit Menu options until you reach the
TRIP VALUE screen, press the Enter button. Use the up
Scroll arrow to increase the value or the down Scroll arrow
to decrease the value. The range is from 0 to 124 percent.
When the desired choice is displayed, press Enter to lock in the selection.
If the procedure completes successfully, Download OK appears briefly. The display
then returns to the previous screen.
4.10.12 Message to Outputs A1 and A2 (IQ 330 & IQ 330M Base Module
Only)
Scroll up or down the Edit Menu options, when you reach either the A1 or A2
Message Display, shown in figures 4.40 and 4.41, press the Enter button.
Note that the second word on this screen indicates the selection made in the Digital
Output Setting, either Message, Voltage, Phase or Null. The below example
represents the message screen if Phase was chosen for both A1 and A2 Digital
Outputs.
The screens also indicate the selection of the message to be sent to either of the
two outputs. The initial result should be NULL. This means if you exit no message
will be sent.
To select the message to be assigned to output A1 or A2, press either of the Scroll
arrows to step through the choices SET, CLEAR or NULL. When the desired choice
is displayed, press Enter to lock in the selection.
The possible selections will be determined by the choices made in Output A Setup.
A Message choice will let you chose all possibilities.
A Voltage choice will let you chose NULL or CLEAR.
A Phase choice will not let you send a message to that output.
A1 PHS NUL
Figure 4.40 Output
A1 Message
Display
Effective Date: 2/04
For more information visit:
IQ 300
Effective Date: 2/04
2
Figure 4.41 Output
A2 Message
Display
www.cutler-hammer.eaton.com
TRIP VALUE
Figure 4.39 Trip
Value Display
2
A2 PHS NUL
IL17574C
Page 4-25