Exit; Edit Set Points (3 And 4 Wire Systems) - Eaton Cutler-Hammer IQ 300 Series Instructions For Installation, Operation And Maintenance

Table of Contents

Advertisement

In PHASE mode the output will be in closed state when the three phase voltages
are in phase and the open state when the three phase voltages are out of phase.
When in Voltage mode the output will be closed when the voltage strays from the
100% nominal reading. The nominal readings will be 120,
240, 480 and 575. The programmable trip value will
determine when the output will be closed. If the rms
voltage drops below a percentage less than 100% the
relay will be closed. If the rms voltage goes above a
percentage that is above 100% the relay will be closed. In
both cases the relay will stay closed until open by a
message. For example if the nominal voltage is 480 V and
you want the unit to trip if the voltage drops below 420 V,
multiply 420 by 100 and divide it by 480 to find your
setting.
To view the status of the trip value scroll up or down on the view setpoints menu to
TRIP VALUE, see figure 4.24.
Note: the MODBUS and INCOM forms of communication do not read the output
values. Refer to 4.10.8 notes for information on entering proper nominal readings.

4.9.11 Exit

To exit the view setpoints options scroll up or down the
menu options till you reach EXIT SMENU, see figure 4.25,
press the enter button.
4.10

EDIT SET POINTS (3 AND 4 WIRE SYSTEMS)

These screens, shown in figure 4.26, permit the user to
change all of the IQ 300 set points and system parameters.
Select EDIT SETPT from the main menu options. If the Password option has been
enabled, the system requests the password.
To enter the password, press the enter button to move the blinking number to the
desired digit. Then use the Scroll up arrow to increase the digit or the Scroll down
arrow to decrease the digit. When the desired choice is displayed, press enter to
lock in the selection.
If an incorrect password is entered, the message ERROR displays. Press Menu to
return to the previous screen showing Edit Set Points. Press Enter to retry entering
the password.
If the correct password is entered, or if the Password option is not enabled, the
screens shown in figure 4.26 will be available. Use the scroll arrows to move
through the screens.
Effective Date: 2/04
For more information visit:
IQ 300
Effective Date: 2/04
www.cutler-hammer.eaton.com
IL17574C
Page 4-17
XX
TRIP VALUE
Figure 4.24 Trip
Value Display
EXIT SMENU
Figure 4.25 Exit
Menu Display
Page 4-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents