15.3
System Alarms Display Map
Display Points
Alarm Point
33
Unit reset
34
NTP Failed
35
Timed Tick
36
Serial 1 RcvQ full
Dynamic memory
37
full
38
Notification 1 failed
39
Notification 2 failed
40
Notification 3 failed
41
Notification 4 failed
42
Notification 5 failed
43
Notification 6 failed
2
44
Notification 7 failed
45
Notification 8 failed
Default
57
Configuration
58
Dip Sw itch Config
MAC Address Not
59
Set
60
IP Address Not Set The IP Address is not set
LAN hardw are
61
error
SNMP processing
62
error
SNMP community
63
error
LAN TX packet
64
drop
Description
Unit has rebooted.
Communication w ith Netw ork Time Server has
failed.
Toggles state at constant rate as configured by
the Timed Tick timer variable. Useful in testing
integrity of SNMP trap alarm reporting.
Serial port 1 (or appropriate serial port number)
receiver filled w ith 8 K of data (4 K if BAC
active)
Not expected to occur.
A notification 1 event, such as a page or email,
w as unsuccessful.
A notification 2 event, such as a page or email,
w as unsuccessful.
A notification 3 event, such as a page or email,
w as unsuccessful.
A notification 4 event, such as a page or email,
w as unsuccessful.
A notification 5 event, such as a page or email,
w as unsuccessful.
A notification 6 event, such as a page or email,
w as unsuccessful.
A notification 7 event, such as a page or email,
w as unsuccessful.
A notification 8 event, such as a page or email,
w as unsuccessful.
Communication w ith Netw ork Time Server has
failed.
Toggles state at constant rate as configured by
the Timed Tick timer variable. Useful in testing
integrity of SNMP trap alarm reporting.
The MAC Address is not set
The unit does not have a solid LAN link to the
hub, sw itch, or router
SNMP trap address is not defined and an SNMP
trap event occurred..
Community string does not match your SNMP
master's community string.
An error occurred transmitting data over LAN.
Solution
If unintentional, call DPS Tech Support: (559) 454-
1600.
Try pinging the Netw ork Time Server's IP
Address as it is configured. If the ping test is
successful, then check the port setting and
verify the port is not being blocked on your
netw ork.
To turn the feature off, set the Timed Tick timer to
0.
Check proxy connection. The serial port data may
not be getting collected as expected.
Call DPS Tech Support (559) 454-1600
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Use RPT filter debug to help diagnose notification
problems.
Try pinging the Netw ork Time Server's IP
Address as it is configured. If the ping test is
successful, then check the port setting and
verify the port is not being blocked on your
netw ork.
To turn the feature off, set the Timed Tick timer to
0.
Call DPS Tech Support - (559) - 454-1600
See Section "Quick Start: How to Connect to the
NetGuardian 16A via Craft Port." If not using the
NetGuardian over LAN, set the IP address to
255.255.255.255
If connecting to a hub, you might require a LAN
crossover cable
Check proxy connection. The serial port data may
not be getting collected as expected.
Verify both community strings to make sure they
match.
Verify that you can ping both devices.
73
Need help?
Do you have a question about the NetGuardian 16A and is the answer not in the manual?
Questions and answers