2
2
Specifications
Discrete Alarm Inputs:
Temperature Sensors:
Sensor Thresholds:
D-wire Sensors:
Multi-purpose User Analogs:
Analog Input Range:
Analog Accuracy:
Analog Thresholds:
Control Relays:
Ping Targets:
Protocols:
Dimensions:
Weight:
Mounting:
Power Input
Voltage Options Include:
Current Draw:
GMT Fuse:
(Optional) Sensor Power Output
Voltage Output:
Output Current:
GMT Fuse:
Interfaces:
Visual Interface:
Audible Notification:
Operating Temperature:
Operating Humidity:
MTBF:
Windows Compatibility:
RoHS:
20
(Optional) 16
Support for up to 32 D-Wire Sensors (see below)
4 per sensor
Up to 32 sensors
16
(Optional) 2 for monitoring power input
-90 to +90 VDC (or 4-20mA)
+/- 1% of Analog Range (See Analog Step Sizes)
4 per analog channel
4
(Optional) 8
16
SNMP (v1, v2c, and v3), DCPx, TELNET, HTTP, SMTP, ICMP, HTTPS
1.72" H x 17.026" W x 6.636" D
(4.4 cm x 43.25 cm x 16.85 cm)
4 lbs. 3oz. (1.9 kg)
19" or 23" rack mount
-48VDC (-36 to -72 VDC)
(Optional) +24 VDC (18 V to 36 VDC)
(Optional) -24VDC (-18 to -36 VDC)
250mA for -48VDC
Resettable Fuse (Internal), if +24V Power Input
-48V or -24V Power Input uses 3/4 Amp GMT Fuse
+12 VDC
Up to 750 mA at +12 VDC
3/4 Amp recommended
1 RJ45 10/100BaseT full-duplex Ethernet port
1 USB front-panel craft port
1 Push button switch
1 RJ11 for DPS sensor network (D-Wire)
2x8 analog connectors
Wireless antenna (Optional)
Serial port options: RS232, RS485, 202, or 33.6k
7 Front Panel LEDs
6 Back Panel LEDs
(Optional) Alarm speaker with volume control
32°–140° F (0°–60° C)
0%–95% non-condensing
60 years
Windows 95, 98 NT, ME, XP, 2000, Vista, 7 32/64 bit
5/6
Need help?
Do you have a question about the NetGuardian 16A and is the answer not in the manual?