Connecting The Communications Connector - Omron DeviceNet DST1 Series Operation Manual

Safety i/o terminals
Hide thumbs Also See for DeviceNet DST1 Series:
Table of Contents

Advertisement

Crimping Tool for Ferrules
IMPORTANT
Use ferrules when wiring cables.
I/O connectors are detachable. Tighten the screws on the I/O connector to 0.25 to
0.3 N
The I/O connector has a structure that helps prevent incorrect wiring. Make
connections at the specified locations corresponding to the terminal numbers.
Do not remove the label from the DST1 before wiring.
Always remove the label after completing wiring to ensure proper heat dispersion.
2-4

Connecting the Communications Connector

Colored stickers are provided on the communications connector that match the colors
of the lines to be inserted. Check that the colors of the lines and stickers match when
wiring the connectors. The colors are as follows:
Color
Red
White
Blue
Black
Refer to the DeviceNet Operation Manual (Cat.No.W267) for details on communications
specifications and wiring.
IMPORTANT
When connecting the communications connector to the DST1, tighten the
screws on the communications connector to 0.25 to 0.3 N
OMRON's S8
power.
Note • The internal power for the DST1-series Safety I/O Terminals is supplied from
the communications power supply (V+, V-).
2-4 Connecting the Communications Connector
Manufacturer
Phoenix Contact
m.
Power cable positive side (V+)
High side of communications data (CAN_H)
-
Shield
Low side of communications data (CAN_L)
Power cable negative side (V-)
Power Supplies are recommended for communications
Model
CRIMPFOX UD6
Signal
m.
2-5