The following table gives the safety input specifications for the DST1-MRD08SL-1.
Input type
ON voltage
OFF voltage
OFF current
Input current
5-3-2

Test Output Specifications

The following table gives the test output specifications for the DST1-MRD08SL-1.
Output type
Rated output current
Residual voltage
Leakage current
5-3-3

Safety Output Specifications for Relay Outputs

The following table gives the safety output specifications for the DST1-MRD08SL-1.
Relays
Minimum applicable load
Rated load for a resistive load
Rated load for an inductive load
Life expectancy
Item
Sinking input (PNP)
11 VDC min.
5 VDC max.
1 mA max.
6 mA
Item
Sourcing output (PNP)
0.7 A
1.2 V max.
0.1 mA max.
Item
Mechanical life
expectancy
Electrical life
expectancy
5-3 Safety I/O Terminal with Relay Outputs
Specifications
Specifications
Specifications
G7SA-2A2B
EN50205 Class A
1 mA at 5 VDC
240 VAC: 2 A
30 VDC: 2 A
2 A at 240 VAC (cos ø=0.3)
1 A at 24 VDC
5,000,000 operations min.
(at approx. 7,200 operations/h)
100,000 operations min.
(at rated load and approx. 1,800 operations/h)