Safety Output Errors - Omron DeviceNet DST1 Series Operation Manual

Safety i/o terminals
Hide thumbs Also See for DeviceNet DST1 Series:
Table of Contents

Advertisement

6-2-3

Safety Output Errors

Code
Error
01
Configuration invalid
hex
02
Over current detected
hex
03
Short-circuit detected
hex
04
Stuck-at-high detected
hex
05
Error in the other dual
hex
channel output
06
Internal relay relevant
hex
circuit error
07
Relay failure
hex
08
Dual channel violation
hex
09
Cross connection
hex
detected
Explicit Message for Reading the Cause of the Error
Explicit
Read/
message
write
Safety Output
Read
Cause of Error
Information
Read
Note: The instance numbers for safety outputs 0 to 7 are 1 to 8 (01 to 08 hex), respectively.
Probable cause
The configuration is invalid.
Trouble with the connected device
Ground fault of the output signal
line
1) The power source (positive side)
is in contact with the output
signal line.
2) Trouble with the internal circuit
Dual channels are set and an error
occurred in the other channel.
Trouble with the internal circuit (MRD
only)
Trouble with the relay (MRD only)
Wrong setting for output data
Short-circuit between output signal
lines.
Function
Service
code
Reads the cause
0E hex
for the normal flag
(1 to 8) specified
by the instance ID
turning OFF.
(See note.)
Configure the DST1 correctly.
Replace the connected device.
Check the wiring.
1) Check the wiring.
2) Replace the DST1.
Remove the error in the other
channel.
Replace the DST1.
Replace the relay.
Check the program.
Check the wiring.
Command
Class
Instance
Attribute
ID
ID
ID
3B
01 to 08
6E hex
hex
hex
6-2 Troubleshooting
Countermeasure
Response
Data
size
-
0: No error
01 hex: Configuration
invalid
02 hex: Overcurrent
detected
03 hex: Short-circuit
detected
04 hex Stuck-at-high
detected
05 hex: Error in the other
dual channel output
06 hex: Internal relay
relevant circuit error
07 hex: Relay failure
08 hex: Dual channel
violation
09 hex: Cross connection
detected
6-5