2-5 Node Address
2-5
Node Address
Set the node address using the two rotary switches on the front panel of the
DST1-series Safety I/O Terminals. The default setting is 63. Set the tens digit of the
node address (decimal) using the left rotary switch and set the ones digit using the right
rotary switch. A value between 00 and 63 can be set.
If a node address between 64 and 99 is set, the node address can be set from the
Network Configurator.
•
The node address must be set while the communications power supply is
turned OFF.
•
Do not change the rotary switches while the power is ON. The DST1-series
IMPORTANT
Safety I/O Terminals will detect this as a change in the configuration and
will switch to fault state.
•
Use a small flat-blade screwdriver to set the rotary switches, being careful
not to scratch them.
2-6
Configuration
Configure the DST1-series Safety I/O Terminals using the Network Configurator.
Refer to Section 3 Configuration for details on settings. Refer to the System
Configuration Manual (Cat.No.Z905) for Network Configurator operating procedures.
2-6
Ones digit of node address
Tens digit of node address