S&C IntelliRupter PulseCloser Manual page 29

Fault interrupter
Hide thumbs Also See for IntelliRupter PulseCloser:
Table of Contents

Advertisement

Local Battery Indication
The LED flash pattern for Local Battery Indication (½ second on, ½ second off) can be
turned on or off. This should be set to the Off setting when no battery is installed because
a Low Battery or Bad Battery indication is unnecessary.
Remote Off Indication
The LED flash pattern (solid on) indicating the Remote Operation mode is set to the
Off mode can be turned on or off, and the default is the Off setting.
Blink Pattern Priority
Only one blink pattern can be displayed at a time. The highest priority condition (indicated
by lower number) will always be displayed:
1. Error (or Battery Low/Bad if enabled) = Flashes ½ second every second
2. Remote Off = Solid On (A Manual Lever command causes a temporary 10-second solid
On.)
3. Wi-Fi connected = Pulses Dim to Bright
4. Loop Restoration is timing or Ready or IntelliTeam is Ready = Flashes 3 times
(½ second On—½ second Off) every 30 seconds
5. Normal operation = On ½ second every 30 seconds
6. IntelliRupter fault interrupter not powered or inoperative = Off
Open Source Operation Screen Control
When this setpoint is set to the Show Control mode, the Open-Source Sectionalizing
(Enabled/Blocked) button is shown at the lower-right side of the Operation screen.
Block Manual Lever If Maintenance Mode (R2 control only)
When the Block Manual Lever If Maintenance Mode setpoint is set to the Yes state
and the External Interface Maintenance Mode input is active, the OPEN and CLOSE
manual control levers and the Operation screen Open and Close commands will be
prevented from opening or closing the IntelliRupter fault interrupter.
Block External Trip Inputs When Maintenance Mode (R2 control only)
When the Block External Trip Inputs When Maintenance Mode setpoint is set to
the Yes state and the External Interface Maintenance Mode command is active, the
External Interface Trip, Open, and Close commands will be prevented from opening
or closing the IntelliRupter fault interrupter.
General Setup