Communication Setup

DNP Diagnostics

160
S&C Instruction Sheet 766-530
Peer Communications Statistics Configuration Section
Acknowledge Coach Messages Every "N" Messages
This configures the number of messages required before an acknowledgement is sent,
where "N" is the number of messages. When 10 is entered, every 10th coach message will
be acknowledged. (Range: 1-100; Step: 1; Default: 1) See Figure 94.
Figure 94. The Setup>Communications>DNP Diagnostics screen.
Acknowledge Runner Messages Every "N" Messages
This configures the number of messages required before an acknowledgement is sent,
where "N" is the number of messages. When 10 is entered, every 10th runner message
will be acknowledged. (Range: 1-100 and NoAck; Step: 1; Default: NoAck)
Good Link Health Threshold
This configures the percentage of successful message transmissions that will define good
link health. (Range: 85-99; Step: 1; Default: 95)
Marginal Link Health Threshold
This configures the percentage of successful message transmissions that will define
marginal link health. (Range: 5-84; Step: 1; Default: 25)
Other DNP V3 Addresses to Monitor Section
DNP Addresses
These DNP addresses can be monitored; check the box to select the addresses. (Default:
Unchecked)
Activate button
Every time a DNP address is checked or unchecked for monitoring, click on the Activate
button.
Last Activation Time
This timestamp indicates the last time the Activate button was clicked.