DNP Analog Input
Points
The screen shown in Figure 98 has configuration parameters for analog input points. Map
these points to make them available in your SCADA system.
Figure 98. The Setup>Point Mapping>Analog Inputs screen.
Analog Point
This is the point number seen by the SCADA system in response to a static request, event
data request, or an unsolicited event response.
Code-Description
These are the point codes that represent specific analog inputs that may be assigned to
individual SCADA point numbers. Setting a code-description to the End option defines
the end of the configured points list and the maximum number of analog inputs that can
be returned.
Analog input points received from the external device may be mapped to individual
SCADA points. Enter the external device analog point number (the range is 0 to 255) in
this column. See the external device documentation for definitions of its analog points.
Event Class
This is the DNP event class assigned to this point. Specify the Class 1, Class 2, or
Class 3 setting, or choose the No Event setting to turn off event data reporting for this
point.
Communication Setup
S&C Instruction Sheet 766-530
165