STEP 7.
Configure the Test 1 TCC Curves setpoint. By using the default Use Previous
TCCs value, the Test 1 and Test 2 TCC curves will use the same Use Previous
TCCs value configured for the Initial Trip setpoint, if a PulseClosing
Technology operation does not detect a fault and the IntelliRupter fault
interrupter closes. Configure TCC curves for both Direction 1 and Direction 2.
See Figure 72.
Figure 72. The PulseFinding technique setpoint on the Setup>Protection>General Profile 1>
Direction 1>Current>Initial Trip - Additional Features screen for Test 1.
Loop Restoration
S&C Instruction Sheet 766-530