Communication Setup
Data Types Section
This section configures each message sent in a scheduled test. The predefined data
types messages sent are not actual coach or runner messages, but they're configured
to represent the approximate size of an actual average coach or runner message. The
Definable Data Types setting allows defining message byte size for the sent and
received messages.
Predefined Data Types
The Connection ID in Row 0 is always configured "Coach" and Row 1 is always configured
"Runner." The Bytes Sent and Bytes Received fields are not configurable.
Definable Data Types
The Connection IDs in Row 2 and 3 are always configured "Undefined" whereas the Bytes
Sent and Bytes Received fields are user defined. If one "Unused" entry is changed, a
numerical entry must also be entered for the other field in that row.
Row
This identifies the row: 0 is the first message type sent, 1 is the second message type
sent, etc.
Data Type
This is the name of the configured test message, such as "Coach" or "Runner." The message
sent is not an actual coach or runner message, but it should be configured to represent
the approximate size of the average coach or runner message by setting the appropriate
number of sent and received bytes.
Bytes Sent
This field configures the length of the message being sent for this type. (Range: 1-2048
and Unused, Step: 1, Default: Unused)
Bytes Received
This field configures the length of the response message automatically generated when
the remote node receives the sent message. (Range: 1-2048 and Unused, Step: 1, Default:
Unused)
S&C Instruction Sheet 766-530
159