4098 Truealarm Sensor Bases; General Notes; Specifications; Setting The Base's Address - Simplex 4098 Applications Manual

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 TrueAlarm SENSOR BASES

General Notes

Specifications

4098-9789
Sensor Base PID
(w/ Remote
LED)
Working Voltage
24-40 VDC
(MAPNET II/IDNet)
24V Working
Voltage (Relay or
Sounder Power)
MAPNET II/IDNet
400 µA
Current *
24V Standby
Current (Relay or
Sounder)
24V Current
(Relay or Sounder
Activated)
LED Output
Yes
Sounder Output
* MAPNET II/IDNet current with Photo Sensor plugged into Base

Setting the Base's Address

TrueAlarm smoke/heat sensor bases are connected to a 2120 Multiplex
Communicating Device Transponder (CDT), 4020, 4100+, 4120, or 4010 panel by a
single wire pair (MAPNET II/IDNet). The 4098-9792, -9789, -9793, and -9796
bases and their sensors obtain both power and data over MAPNET II/IDNet wiring.
The 4098-9791 sensor base requires 24VDC power for relay operation and the
4098-9794 and 4098-9795 sensor base with sounder requires 24 VDC or
Notification Appliance Circuit (NAC) power. The 4098-9791, -9794, -9795, and
-9796 are NOT compatible with the 2120 CDT. The 4098-9793 is only compatible
with the 4010 panel.
Table 6 contains the specifications for the TrueAlarm Sensor Bases.
Table 6. TrueAlarm Sensor Bases Specifications
4098-9791
(w/ Relay and
4098-9792
Remote LED)
24-40 VDC
24-40 VDC
18 – 32 VDC
400 µA
400 µA
270 µA
28 mA
Yes
Each sensor base has a unique address. This address is associated with a custom
label that identifies its physical location within a building. The base's address and
location must match up with the address listed in the specification sheets of the
2120 Job Configuration Report or the Programmer's Report for the 4020, 4100+,
4120, or 4010 System. See Figure 9 for DIP Switch location for 4098-9789, -
9791, -9792, -9793, and -9796 Sensor Bases. See Figure 10 for DIP Switch
location for 4098-9794 and 4098-9795.
26
firealarmresources.com
4098-9793
4098-9794
(Isolator Base)
(Sounder Base)
24-40 VDC
24-40 VDC
18 – 32 VDC
500 µA
400 µA
270 µA
17 mA
Yes
88dBA
minimum
4098-9796
4098-9795
(Multi-Sensor
(Multi-Sensor
w/ Remote
Sounder Base)
LED)
24-40 VDC
24-40 VDC
18 – 32 VDC
500 µA
500 µA
270 µA
17 mA
Yes
Yes
88dBA minimum
Continued on next page