Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 TrueAlarm SENSOR BASES,
Setting the Base Address
(continued)
Continued
DIP Switches
Figure 9. 4098-9789, -9791, -9792, -9793, -9796 Sensor Bases
Location of DIP Switches
"ON" Position
DIP Switches
"OFF" Position
Note: The 4098-9794 Sounder Base and 4098-9795 Multi-Sensor Sounder Base
have a 9-position DIP Switch. The first eight DIP Switches set the
sounder base address. Dip Switch position 9 is set to OFF or ON
depending upon the sounder base power source. When the sounder base
is connected to a 24 VDC power source, DIP switch position 9 is set to
"OFF" and the 24 VDC power is supervised by the sounder base. When
the sounder base is powered by the panel's Notification Appliance Circuit
(NAC), DIP Switch position 9 is set to "ON" and the power is supervised
by the NAC and not the sounder base.
Figure 10. 4098-9794 and 4098-9795 Sensor Bases Location of
DIP Switches
27
firealarmresources.com
1 2 3 4 5 6 7 8
DIP Switch Position 9 "ON"
DIP Switch Position 9 "OFF"
for 24 VDC Power Input
for NAC Power Input