ACCESSORIES, Continued
Relay Modules (continued)
4098-9822 Relay Module Wiring
The 4098-9822 Relay Module is used with the 4098-9789, -9791, -9794, -9795,
and -9796 Sensor Bases and the 4098-9713 QuickConnect Sensor with Sounder.
Install the relay module using Figure 15 and 21 as a reference.
Important:
Do not use a remote LED if using the 4098-9822 relay module.
The 4098-9822 relay module is not supervised and should only
be used for non-critical supplementary functions. There is a
limit of ten control outputs activated on a MAPNET II/IDNet
channel. If the channel capacity is exceeded, the relay module
may not function properly.
+24VDC
FROM
PANEL
0V
(IF USED)
(SEE NOTE 2)
CENTER
CONTACT B
N.C.
(SEE NOTE 3)
N.O.
Notes:
1.
Do not use remote LED
2.
18 to 32 VDC, .008 amps typical / .013 amps. Maximum
3.
Contact A or B: Dry, Form "C" - each rated 2 amps resistive at 24 VDC/0.5 amps
at 110 VAC, resistive.
Figure 21. 4098-9822 Relay Module Wiring
39
firealarmresources.com
+24VDC
TO OTHER 24VDC
DEVICES OR
0V
SUPERVISORY MODULE
(SEE NOTE 1)
-BLUE
+WHITE
WHITE
BLUE
RED
RED
4098-9822
RELAY
BLACK
BLACK
BROWN
ORANGE
CENTER
VIOLET
YELLOW
N.C.
GREY
GREEN
N.O.
Continued on next page
FROM 4098-9789, -9791,
-9794,-9795, -9796
SENSOR BASE OR
4098-9713 QUICKCONNECT
SENSOR with SOUNDER
CONTACT A
(SEE NOTE 3)