4098 BASES, Continued
Wiring (continued)
Notes:
1.
If used, 4098-9830 remote LED is polarized;
refer to Figure 8 to wire remote LED to Heat
detector; observe color-coded wiring.
2.
Wire only one relay base per initiating circuit.
3.
For Style D initiating circuit, wire per dotted
lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams
provided with the system panel for proper EOL
resistor value.
4.
It is recommended that the primary-1 and the
backup-2 lines be in separate wire runs and in
compliance with local requirements.
5.
Aux. Relay contacts, each rated 1 amp at
28 VDC/0.5 amp at 125 VAC, resistive.
Figure 6. 4098-9683 2-Wire Relay Base Connections for Style B or D Initiating Circuits
BACKUP 2
SEE NOTE 4
-
+
INITIATING
PRIMARY 1
CIRCUIT
SEE NOTE 4
+
-
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+,
4004, OR 4005
21
firealarmresources.com
SEE
SEE NOTE 3
NOTE
3
RESISTOR
(IF USED)
VIO
RED
BLU
GRY
BLK
RED
BLK
YEL
ORN
BLK
GRN
REMOTE LED
4098-9830
(SEE NOTE 2)
(SEE NOTE 1)
EOL
N/C
C
AUX. RELAY CONTACTS, EACH
N/O
(See Note 5)
RATED 1 AMP AT 33 VDC
N/C
RESTRICTIVE
C
N/O
Continued on next page