4098 BASES, Continued
Wiring (continued)
INITIATING
CIRCUIT
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+,
4004, OR 4005
Notes:
1.
If used, 4098-9830 remote LED is polarized;
observe color-coded wiring.
2.
It is recommended that the primary-1 and the
backup-2 lines be in separate wire runs and in
compliance with local requirements.
3.
For Style D initiating circuit, wire per dotted
lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams
provided with the system panel for proper EOL
resistor value.
Figure 8. 4098-9684 Heat Detector LED Base Connections for Style B or D Initiating Circuits
BACKUP 2
SEE NOTE 2
-
SEE NOTE 3
+
PRIMARY 1
SEE NOTE 2
+
4098-9684
-
HEAT DETECTOR
BASE
RED
BROWN
BLK
BLK
WHITE
firealarmresources.com
4098-9684
HEAT DETECTOR
BASE
4098-9830
REMOTE LED
(SEE
NOTE 1)
RED
BLK
BLK
23
SEE
NOTE
3
EOL
RESISTOR
(IF USED)
4098-9830
REMOTE LED
(SEE
NOTE 1)
BROWN
WHITE