MAINTENANCE AND TESTING, Continued
Testing (continued)
.
Figure 24
Magnet Test Location for 4098-9601, -9602, -9603, -9605
Smoke Detectors using 553-810 Magnet Tester
Table 10. MAG TEST/Normal Modes - States and Reactions
STATE
Normal Mode
(LED flashes
every 4 secs.)
Normal
X
More Sensitive
X
Less Sensitive
X
Non-Functional
When placing the magnet at the location indicated by a "" mark embossed on
the cover, the visible LED flashes indicating the detector's condition. The
following are descriptions of what you should see when using the MAG TEST.
NORMAL - When in MAG TEST, the detector latches into alarm if the
detector is within calibration range and the visible LED stays ON.
MORE SENSITIVE - When in MAG TEST, if the detector is more
sensitive than the maximum calibration, the visible LED quickly flashes,
twice a second. Following the sixth flash, the detector latches into alarm
and the visible LED stays ON.
45
firealarmresources.com
MAG TEST Mode
LED Flashes
LED Flashes
Quickly 6 Times
Slowly 4 Times
X
X
X
Continued on next page
Latches in Alarm
Mode/LED stays
"ON"
X
X