Simplex 4098 Applications Manual page 39

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 TrueAlarm SENSOR BASES,
Wiring (continued)
IDNet
FROM
4010
PANEL
IDNet
SHIELD IS OPTIONAL
(SEE NOTE 3)
Notes:
1.
Isolator base compatible with 4010 panel ONLY.
2.
Maximum quantity of devices per circuit is 250 for 4010 panel.
3.
If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated from electrical box.
Continued
Figure 16 shows the wiring connections for the isolator sensor base. All screw terminals accept 14 to 18-gauge AWG solid or
stranded. Maximum torque should not exceed 12-inch-pounds.
Caution: Do not loop wire under terminals. Break wire runs to provide supervision.
SHIELD
Figure 16. 4098-9793 Isolator Sensor Base Connections
firealarmresources.com
SHIELD
33
IDNet
TO OTHER
IDNet DEVICES
(SEE NOTE 2)
IDNet
SHIELD

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents