Simplex 4098 Applications Manual page 22

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 HEAT DETECTORS, Continued
Specifications (continued)
Product ID
4098-9612
4098-9613
4098-9614
4098-9615
Table 4. Heat Detector Specifications
Description
Application
Fixed-Temp.
Unusually violent
temp. fluctuations &
Only, 135° F
ceiling temperatures
(57° C)
not exceeding
100° F (38° C)
Fixed-Temp.
Normal temp.
and Rate-of-
fluctuations & ceiling
temperatures not
Rise, 135° F
exceeding 100° F
(57° C)
(38° C)
Fixed-Temp.
Unusually violent
temp. fluctuations &
Only, 200° F
ceiling temperatures
(93° C)
exceeding 100° F
(38° C) but not
150° F (68° C)
Fixed-Temp. &
Normal temp.
Rate-of-Rise,
fluctuations & ceiling
temperatures
200° F (93° C)
exceeding 100° F
(38° C) but not
150° F (68° C)
16
firealarmresources.com
Max. Spacing
FM
Allowed (UL)
60 X 60 ft
15 X 15 ft
(18 X 18 m)
(4.6 X4.6 m)
70 X 70 ft
30 X 30 ft
(21 X 21 m)
(9.2 X 9.2 m)
60 X 60 ft
15 X 15 ft
(18 X 18 m)
(4.6 X4.6 m)
70 X 70 ft
30 X 30 ft
(21 X 21 m)
(9.2 X 9.2 m)