Run Signal - Hitachi CONVENTION 14 Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when
it is in Run Mode. The output logic is
active low, and is the open collector type
(switch to ground).
Option
Terminal
Code
Symbol
00
RUN
Run Signal
Valid for inputs:
11, AL0 – AL2
Required settings
(none)
Notes:
The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082
start frequency is the initial inverter output
frequency when it turns ON.
The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the
coil from damaging the inverter's output
transistor.
Function Name
State
ON
OFF
.
The
1
[FW,RV]
0
B082
Output
frequency
1
Run
0
signal
Description
when inverter is in Run Mode
when inverter is in Stop Mode
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
AL1
Power
supply
See I/O specs on
page 4-6
4 − 39
4 39
start freq.
ON
t
page
3-54):
RUN
11
RY
page 4-35 and
3-54):
RUN
AL2
Load