Hitachi CONVENTION 14 Instruction Manual page 127

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

3 − 44
3 44
B089: Monitor display select for networked inverter – When the X200 inverter is
controlled via network, the inverter's keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 will be displayed on the keypad. See
"Local Monitoring During Network Operation" on page 3-8
B092: Cooling Fan Control – You can select the performance of the cooling fan (if your
inverter model includes a fan). This function controls whether the cooling fan stops or
keeps on running after the inverter stops the motor. This can result in an additional
energy saving and extends fan life.
Func.
Code
B089
Monitor display select for
networked inverter
PANEL
B092
Cooling fan control
FAN-CTRL
"B" Function
Name /
SRW Display
Selects the parameter displayed on the
keypad display when the inverter is
networked, 7 options:
01 Output frequency monitor
02 Output current monitor
03 Rotation direction monitor
04 Process variable (PV), PID
05 Intelligent input terminal status
06 Intelligent output terminal status
d001
07 Scaled output frequency monitor
Selects when the fan is ON during
inverter operation, three options:
00 Fan is always ON
01 Fan is ON during run, OFF during
OFF
02 Fan is temperature controlled
Description
feedback monitor
stop (5 minute delay from ON to
OFF)
for more details.
Defaults
Run
Mode
-FE
-FU
Edit
(EU)
(USA)
01
01
00
00
Units