"A" Group: Standard Functions

The inverter provides flexibility in how you control Run/Stop operation and set the
output frequency (motor speed). It has other control sources that can override the A001
/ A002 settings. Parameter A001 sets the source selection for the inverter's output
frequency. Parameter A002 selects the Run command source (for FW or RV Run
commands). The default settings use the input terminals for –FE (European) models,
and the keypad for –FU (USA) models.
Func.
Code
A001
Frequency source setting
F-COM
A201
Frequency source setting,
2nd motor
2F-COM
A002
Run command source setting
OPE-Mode
A202
Run command source setting,
2nd motor
OPE-Mode
Frequency Source Setting – For parameter A001, the following table provides a further
description of each option, and a reference to other page(s) for more information.
Code
00
01
02
03
10
"A" Function
Name /
SRW Display
Five options; select codes:
00
VR
01
02
03
10
VR
Three options; select codes:
01
02
REM
03
REM
Frequency Source
Keypad potentiometer – The range of rotation of the knob
matches the range defined by B082 (Start frequency
adjustment) to A004 (Maximum frequency setting)
Control terminal – The active analog input signal on analog
terminals [O] or [OI] sets the output frequency
Function F001 setting – The value in F001 is a constant,
used for the output frequency
ModBus network input – The network has a dedicated
register for inverter output frequency
Calculate function output – The Calculated function has
user-selectable analog input sources (A and B). The output
can be the sum, difference, or product (+, -, x) of the two
outputs.
Description
Keypad potentiometer
Control terminal
Function F001 setting
ModBus network input
Calculate function output
Control terminal
Run key on keypad,
or digital operator
ModBus network input
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
01
00
01
00
01
02
01
02
Refer to page(s)...
2-24
4-53, 3-13, 3-28,
3-49
3-9
B-19
3-29