Hitachi CONVENTION 14 Instruction Manual page 280

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

Func.
Name
Code
C044
PID deviation level
setting
C052
PID FBV function high
limit
C053 PID FBV function
variable low limit
C070 Selection of OPE /
ModBus
C071 Communication speed
selection
C072 Node allocation
C074 Communication parity
selection
C075 Communication stop bit
selection
C076
Communication error
select
C077
Communication error
time-out
C078 Communication wait
time
C081
O input span calibration
C082
OI input span calibration R/W Scale factor between the external
C086
AM offset calibration
C091 Debug mode enable
C101
Up/Down memory mode
selection
List of Holding Registers
R/W
Description
R/W Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%, resolution is
0.1%
R/W When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%
R/W When the PV goes below this value,
the PID loop turns ON the PID
second stage output, range is 0.0 to
100%
R/W Two option codes:
02 OPE or option
03 ModBus (485)
NOTE: These network settings are
not accessible to ModBus. Use the
inverter keypad or digital operator
to edit. Refer to
"Network
Communication Settings" on page
3–60.
R/W Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
R/W Offset adjustment of AM output.
Range is 0.0 to 10.0
Adjust together with B080 (AM
gain adjustment)
Displays debug parameters.
Two option codes:
00 Disable
01 Enable
Controls speed setpoint for the
inverter after power sycle.
Two option codes:
00 Clear last frequency (return to
default frequency F001)
01 Keep last frequency adjusted
by UP/DWN
B − 37
B 37
Network Data
Reg.
Range
Res.
1129h 0 to 1000 0.1 %
112Eh 0 to 1000 0.1 %
112Fh 0 to 1000 0.1 %
1137h
2, 3
1138h
1139h
113Bh
113Ch
113Dh
113Eh
113Fh
1141h 0 to 2000 0.1 %
1142h 0 to 2000 0.1 %
1145h
0 to 100
0.1 V
1149h
0, 1