Hitachi CONVENTION 14 Instruction Manual page 140

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

Low Load Detection Parameters
The
following
conjunction with the intelligent output
function, when configured. The output
mode parameter (C038) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (C039) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
Func.
Name /
Code
SRW Display
C038
Output mode of low load
detection signal
LOC MODE
C039
Low load detection level
LOC LVL
parameters
work
"C" Function
Three option codes:
00 Disabled
01 During acceleration, deceleration
and constant speed
02 During constant speed only
CRT
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
02.60A
current
in
Output
current
C039
0
[LOC]
output
1
0
Description
3 − 57
3 57
t
t
Run
Defaults
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
01
01
INV
INV
A
rated
rated
curr.
curr.