Hitachi CONVENTION 14 Instruction Manual page 122

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

Func.
Name /
Code
SRW Display
B050
Selection of controlled stop
operation
IPS MODE
B051
Controlled stop operation
start voltage setting
IPS V
B052
OV-LAD Stop level of
controlled stop operation
setting
IPS OV
B053
Deceleration time of
controlled stop operation
setting
IPS DEC
B054
Frequency drop for quick
deceleration setting
IPS F
"B" Function
Two option codes:
00 Disabled
01 Enabled (stop)
OFF
02 Enabled (restart)
Setting of DC bus voltage to start
controlled stop operation. Range
is 0.0 to 1000.0
0000.0V
Setting the OV-LAD stop level of
controlled stop operation. Range
is 0.0 to 1000.0
0000.0V
Range is 0.01 to 3000
0001.0s
Setting of the first quick drop in
frequency. Range is 0.0 to 10.0
0000.0Hz
Description
3 − 39
3 39
3 39
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
00
00
0.0
0.0
V
0.0
0.0
V
1.0
1.0
sec
0.0
0.0
Hz

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

X200 series

Table of Contents