Hitachi CONVENTION 14 Instruction Manual page 41

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

1 − 20
1 20
Torque and Constant Volts/Hertz Operation
In the past, AC variable speed drives used an
open loop (scalar) technique to control speed.
The
maintains a constant ratio between the
applied voltage and the applied frequency.
With these conditions, AC induction motors
inherently delivered constant torque across
the
operating
applications, this scalar technique was
adequate.
Today, with the advent of sophisticated microprocessors and digital signal processors
(DSPs), it is possible to control the speed and torque of AC induction motors with
unprecedented accuracy. The X200 utilizes these devices to perform complex
mathematical calculations required to achieve superior performance. You can choose
various torque curves to fit the needs of your application. Constant torque applies the
same torque level across the frequency (speed) range.
reduced torque
setting will add additional torque in the lower half of the frequency range for the
constant and variable torque curves. With the
specify a series of data points that will define a custom torque curve to fit your
application.
Inverter Input and Three-phase Power
The Hitachi X200 Series of inverters includes two sub-groups: the 200V class and the
400V class inverters. The drive described in this manual may be used in either the
United States or Europe, although the exact voltage level for commercial power may be
slightly different from country to country. Accordingly, a 200V class inverter requires
(nominal) 200 to 240VAC, and 400V class inverter requires from 380 to 480VAC.
The 200V class inverters having a suffix of –SFE accept single-phase 200V class input
voltage, those with a –NFU suffix single- or three-phase power, and those with a suffix
–LFU three-phase power only. All 400V class inverters require three-phase power
supply.
TIP: If your application only has single phase power available, refer to X200 inverter of
3HP or less (European version with a suffix of -SFE); they can accept single phase input
power. Note: Larger models may be able to accept single-phase with derating. Contact
your Hitachi distributor for assistance.
The common terminology for single phase power is line (L) and Neutral (N). Three-
phase power connections are usually labeled Line 1 [R/L1], Line 2 [S/L2] and Line 3
[T/L3]. In any case, the power source should include an earth ground connection. That
ground connection will need to connect to the inverter chassis and to the motor frame
(see "Wire the Inverter Output to Motor" on page 2-21).
constant-volts-hertz
speed
range.
, lowers the torque delivered at mid-level frequencies. A torque boost
Output
voltage
V
operation
0
For
some
free-setting torque
Constant torque
100%
Output frequency
Variable torque
, also called
curve feature, you can
f

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

X200 series

Table of Contents