Hitachi CONVENTION 14 Instruction Manual page 136

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

Option
Terminal
Function Name
Code
Symbol
50
ADD
ADD frequency
enable
51
F-TM
Force Terminal
Mode
52
RDY *
Inverter Ready
53
SP-SET
Special set
64
EMR *
Emergency
255
-
(No function)
NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F001 or change the value of F001 while the inverter is in Run Mode (motor
running). If it is necessary to check the value of F001 during Run Mode, lease monitor
D001 instead of F001.
HIGH VOLTAGE: When set RDY function ON, there will be a voltage appears at motor
output terminals U, V and W even if the motor is in stop mode. So never touch the
inverter power terminals even the motor is not running.
NOTE: The EMR is not programmable, but will be assigned automatically when the
hardware switch S8 is made ON. When the EMR is assigned, function assignments of
terminal 3, 4 and 5 are automatically changed as follows. Please also refer to
Emergency Stop paragraph.
Default setting
Terminal
Emergency Stop switch
Number
1
2
3
4
CF2 [US ver. :USP]
5
(PTC assignable)
Input Function Summary Table
ON
Adds the A145 (add frequency) value to the output
frequency
OFF
Does not add the A145 value to the output frequency
ON
Force inverter to use input terminals for output
frequency and Run command sources
OFF
Source of output frequency set by A001 and source of
Run command set by A002 is used
ON
To charge up the internal boot-strap capacitor so to
start motor immediately after the RUN command is
given.
OFF
Inverter operates normal.
ON
The inverter uses 2nd motor parameters for generating
frequency output to motor. The selection of 1st or 2nd
motor is available during Stop Mode or Run Mode.
OFF
The inverter uses 1st (main) motor parameters for
generating frequency output to motor.
ON
Inverter recognizes that the emergency signal is given,
Stop
and shuts off the output.
Refer to "Safe Stop" on page 4-32.
OFF
Inverter operates normal
ON
(input ignored)
OFF
(input ignored)
Emergency Stop switch
S8 = OFF
FW
RV
CF1
[HW based for 1b input]
[HW based for 1a input]
RS
Description
Emergency Stop switch condition
Emergency Stop switch
S8 = ON
S8 = ON
FW
RV
EMR
RS
- (No func.)
3 − 53
3 53
OFF
FW
RV
- (No func.)
RS
[Normal 1a]
- (No func.)