Hitachi CONVENTION 14 Instruction Manual page 103

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

3 − 20
3 20
Frequency-related Functions
Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will
apply regardless of the source of the
speed reference. You can configure the
lower frequency limit to be greater than
zero as shown in the graph. The upper
limit must not exceed the rating of the
motor or capability of the machinery.
The
(A004/A204)
frequency upper limit (A061/A261).
Func.
Code
A061
Frequency upper limit setting
Lim H
A261
Frequency upper limit
setting, 2nd motor
2Lim H
A062
Frequency lower limit setting
Lim L
A262
Frequency lower limit
setting, 2nd motor
2Lim L
maximum
frequency
takes
precedence
"A" Function
Name /
SRW Display
0000.0Hz
0000.0Hz
0000.0Hz
0000.0Hz
Output
frequency
Upper
A061
limit
Lower
A062
limit
setting
over
Description
Sets a limit on output frequency
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
0
Frequency command
Run
Defaults
Mode
-FE
Edit
(EU)
(USA)
0.0
0.0
0.0
0.0
Settable
range
-FU
Units
0.0
Hz
0.0
Hz
0.0
Hz
0.0
Hz