4 − 6
4 6

Control Logic Signal Specifications

The control logic connectors are located just
behind the front housing cover. The relay
contacts are just to the left of the logic connectors.
Connector labeling is shown below.
Analog
output
AM H
Terminal Name
[P24]
[PCS]
[1], [2], [3], [4], [5]
[L] (right) *1
[11]
[CM2]
[AM]
[L] (left) *2
[OI]
[O]
[H]
[AL0]
[AL1] *3
[AL2] *3
Note 1:
Note 2:
Note 3:
Relay
contacts
AL2 AL1 AL0
Analog
inputs
Logic inputs
O OI L
5
4
3
Description
+24V for logic inputs
Intelligent input common
Discrete logic inputs
GND for logic inputs
Discrete logic output
GND for logic output
Analog voltage output
GND for analog signals
Analog input, current
Analog input, voltage
+10V analog reference
Relay common contact
Relay contact, normally open
Relay contact, normally closed
The two terminals [L] are electrically connected together inside the inverter.
We recommend using [L] logic GND (to the right) for logic input circuits and
[L] analog GND (to the left) for analog I/O circuits.
Default relay N.O./N.C. configuration is reversed. See
Logic
output
2
1
L PCS P24 CM2 11
Short bar : default position (Source logic)
24VDC, 30mA. (do not short to terminal L)
Factory set: Source type for –FE and –HE
models (connecting [P24] to [1]~[5] turns
each input ON). To change to sink type,
remove the short wire between [PCS] and
[L], and connect it between [P24] and [L]. In
this case, connecting [L] to [1]~[5] makes
each input ON.
27VDC max. (use PCS or an external
supply referenced to terminal L)
Sum of input [1]~[5] currents (return)
50mA max. ON state current,
27 VDC max. OFF state voltage
100 mA: [11] current return
0~10VDC 1mA maximum
Sum of [OI], [O], and [H] currents (return)
4 to 19.6 mA range, 20 mA nominal,
input impedance 250
0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k
10VDC nominal, 10mA max.
250VAC,
250VAC,
100VAC, 10mA min.
30VDC,
30VDC,
5VDC, 100mA min.
Ratings
2.5A (R load) max.
0.2A (I load, P.F.=0.4) max.
3.0A (R load) max.
0.7A (I load, P.F.=0.4) max.