General Specifications - Hitachi CONVENTION 14 Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Table of Contents

Advertisement

1 − 10
1 10

General Specifications

The following table applies to all X200 inverters.
Protective housing *1
Control method
Carrier frequency
Output frequency range *4
Frequency accuracy
Frequency setting resolution
Volt./Freq. characteristic
Overload capacity
Acceleration/deceleration time
Input
Freq.
signal
setting
FWD/
REV run External signal Forward run/stop, Reverse run/stop
Intelligent input
terminal
Output
Intelligent output
signal
terminal
Frequency monitor
Alarm output contact
Other functions
Protective function
Operating
environment
Coating color
Options
Item
IP00
Sinusoidal Pulse Width Modulation (PWM) control
2kHz to 12kHz (default setting: 3kHz)
0.5 to 400Hz
Digital command: 0.01% of the maximum frequency
Analog command: 0.4% of the maximum frequency (25 C
Digital: 0.1Hz; Analog: max. frequency/1000
V/f control (constant torque, reduced torque)
150% rated current for 1 minute
0.01 to 3000 seconds, linear and S-curve accel/decel, second
accel/decel setting available
Operator panel Up and Down keys / Value settings
Potentiometer
Analog setting
External signal
0 to 10 VDC (input impedance 10k Ohms), 4 to 20mA (input
*9
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
Operator panel Run/Stop (Forward/Reverse run change by command)
FW (forward run command), RV (reverse run command), CF1~CF4
(multi-stage speed setting), JG (jog command), DB (external
braking), SET (set second motor), 2CH (2-stage accel./decel.
command), FRS (free run stop command), EXT (external trip), USP
(startup function), SFT (soft lock), AT (analog current input select
signal), RS (reset), PTC (thermistor thermal protection), STA (start),
STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID
reset), UP (remote control up function), DWN (remote control down
function), UDC (remote control data clearing), OPE (operator
control), ADD (add frequency enable), F-TM (force terminal mode),
RDY (Run ready), SP-SET (Special set) , EMR (Emergency Stop)
RUN (run status signal), FA1,FA2 (frequency arrival signal),
OL (overload advance notice signal), OD (PID error deviation
signal), AL (alarm signal), Dc (analog input disconnect detect),
FBV (PID two-stage control output), NDc (network detection signal),
LOG (Logic output), ODc (comm. watchdog error), LOC (Low load)
Analog output; Select output frequency or output current monitor
ON for inverter alarm (1c contacts, both normally open or closed
avail.)
AVR function, curved accel/decal profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, carrier
frequency change (2 to 12kHz) *10, frequency jump, gain and bias
setting, process jogging, electronic thermal level adjustment, retry
func., trip history monitor, 2nd setting select, fan ON/OFF selection.
Over-current, over-voltage, under-voltage, overload, extreme high
temperature, CPU error, memory error, ground fault detection at
startup, electronic thermal
Temperature
Operating (ambient): -10 to 40 C(*10), / Storage: -25 to 70 C(*11)
Humidity
20 to 90% humidity (non-condensing)
Vibration *12
5.9m/s
Location
Altitude 1,000m or less, indoors (no corrosive gasses or dust)
Blue
Remote operator unit, copy unit, cables for the units, braking unit,
braking resistor, AC reactor, DC reactor, noise filter
General Specifications
2
(0.6G), 10 to 55 Hz