Leave a minimum of 30 cm (11.81 in) of clearance at the front and rear of the switch. (Perforated rack
n
doors are acceptable within the 30cm spacing.)
Air flow into and out of the switch is indicated by the arrows in the image below.
Ensure that the rack for the switch is well ventilated, with minimal airflow obstruction at the front and rear.
n
The installation site HVAC system must be capable of removing all heat generated by the switch.
n
Verify that the airflow design of the chassis is compatible with the airflow design of the installation site.
n
Figure 5 Aruba 6405 Switch Cooling Air Flow
Figure 6 Aruba 6410 Switch Cooling Air Flow
Product Weight Support
Make sure the floor can support the total weight of the rack, chassis, modules, power supplies, and all other
components and devices. Take into consideration system expansions (for example, adding more modules
and switches) when you plan the loading capacities.