Levelflex FMP53 FOUNDATION Fieldbus
Level unit
Navigation
Description
Selection
Factory setting
Additional information
Blocking distance
Navigation
Description
User entry
Factory setting
Additional information
Endress+Hauser
 Setup → Advanced setup → Level → Level unit
Select level unit.
SI units
• %
• m
• mm
%
The level unit may differ from the distance unit defined in the Distance unit parameter
(→  128):
• The unit defined in the Distance unit parameter is used for the basic calibration (Empty
calibration (→  129) and Full calibration (→  130)).
• The unit defined in the Level unit parameter is used to display the (unlinearized) level.
 Setup → Advanced setup → Level → Blocking dist.
Specify upper blocking distance UB.
0 to 200 m
For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
No echos are evaluated within the blocking distance UB. Therefore, UB can be used to
suppress interference echos within the upper end of the probe.
 30
Blocking distance (UB) for liquid measurements
US units
• ft
• in
UB