Levelflex FMP53 FOUNDATION Fieldbus
Level unit
Navigation
Description
Selection
Factory setting
Additional information
Blocking distance
Navigation
Description
User entry
Factory setting
Additional information
Endress+Hauser
Setup → Advanced setup → Level → Level unit
Select level unit.
SI units
• %
• m
• mm
%
The level unit may differ from the distance unit defined in the Distance unit parameter
(→ 128):
• The unit defined in the Distance unit parameter is used for the basic calibration (Empty
calibration (→ 129) and Full calibration (→ 130)).
• The unit defined in the Level unit parameter is used to display the (unlinearized) level.
Setup → Advanced setup → Level → Blocking dist.
Specify upper blocking distance UB.
0 to 200 m
For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
No echos are evaluated within the blocking distance UB. Therefore, UB can be used to
suppress interference echos within the upper end of the probe.
30
Blocking distance (UB) for liquid measurements
US units
• ft
• in
UB
Operating menu
A0013219
143