Endress+Hauser Levelflex FMP53 FOUNDATION Fieldbus Operating Instructions Manual page 140

Guided wave radar
Hide thumbs Also See for Levelflex FMP53 FOUNDATION Fieldbus:
Table of Contents

Advertisement

Operating menu
Medium type
Navigation
Description
User interface
Factory setting
Additional information
Medium property
Navigation
Prerequsite
Description
Selection
Factory setting
140
"Level" submenu
Navigation
 Setup → Advanced setup → Level
 Setup → Advanced setup → Level → Medium type
Specify type of medium.
• Liquid
• Solid
FMP50, FMP51, FMP52, FMP53, FMP54, FMP55: Liquid
This parameter determines the value of several other parameters and strongly
influences the complete signal evaluation. Therefore, it is strongly recommended not
to change the factory setting.
 Setup → Advanced setup → Level → Medium property
EOP level evaluation ≠ Fix DC
Specify relative dielectric constant ε
• Unknown
• DC 1.4 ... 1.6
• DC 1.6 ... 1.9
• DC 1.9 ... 2.5
• DC 2.5 ... 4
• DC 4 ... 7
• DC 7 ... 15
• DC > 15
Dependent on Medium type (→  140) and Medium group (→  129).
Levelflex FMP53 FOUNDATION Fieldbus
of the medium.
r
Endress+Hauser

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Levelflex FMP53 FOUNDATION Fieldbus and is the answer not in the manual?

Questions and answers

Table of Contents