Venting Charts - Valor HORIZON 534JN Installation Manual

Direct vent zero clearance gas fireplace
Hide thumbs Also See for HORIZON 534JN:
Table of Contents

Advertisement

Venting
How to Read the Venting Charts
The charts below apply to co-axial roof or wall termina-
tion in installations with vertical rise. See page 17 for
installations with no vertical rise.
1. The total length of the vent pipe cannot exceed
40 feet.
2. The minimum vertical height with roof termination is
10 feet.
3. Any combination of rise and run can be used as long
as they are within the allowable limits shown on the
chart below.
4. A maximum of 4 x 90 degrees elbows—or equivalent
(2 x 45 degrees = 90 degrees)—can be used.

Venting Charts

Allowable Co-Axial Vent Confi gurations with Vertical Rise
Facing Outlet
Rear
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
1
1
2
3
4
5
Horizontal Run (ft)
NO INSTALLATION
3
2
1
1
2
3
NO INSTALLATION
6
8
10
12
14
5. Each 90 degrees elbow installed on the horizon-
tal plane is equivalent to a 3 feet horizontal pipe;
therefore, 3 feet must be subtracted from allowable
horizontal run. (45 degrees elbow is equivalent to
18 inches horizontal pipe.)
6. All horizontal pipe runs must be graded 1/4 inch per
foot upwards in the direction of the exhaust fl ow.
The fi nal pipe length, when terminating through the
wall may be graded downwards slightly to prevent
water migration.
7. Maximum co-linear venting is 40 feet.
8. A restrictor is required for all installations—see
Restrictors page 25 for more information.
Facing Outlet
Top
40
38
36
34
32
30
28
26
24
22
20
18
Example 1
16
14
12
10
8
6
4
2
0.5
16
1
2
3
Horizontal Run (ft)
NO INSTALLATION
3
2
1
0.5
1
2
NO INSTALLATION
4
5
6
8
10
12
Co-axial
3
14
16
19

Advertisement

Table of Contents
loading