Diagnostic Information; Error - Pilz PSEN sc M 3 Series Operating Manual

Table of Contents

Advertisement

Operation
10.3

Diagnostic information

10.3.1

Error

Message in the display
Icon
Text
CLEANW1
INPUTCF1
INPUTCF2
INTF1
INTF2
INTF3
INTF4
INTF5
INTF7
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
Error/cause
The front panel of the safety laser
scanner must be cleaned.
Error in the configuration or the wir-
ing.
Configuration error.
An error occurred during the system
test.
An error occurred during the system
test.
An error occurred during the system
test.
An error occurred during the system
test.
An error occurred during the system
test.
An error occurred during the system
test.
Description/measure
Clean front panel
Check whether the
wiring [
and the
configuration [
match.
In the configuration, check the con-
figured state transitions and switch-
ing operations.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
85].
If the error persists, please contact
Pilz.
48]
70]
will
| 79