Function description
The muting lamp must be connected to the PSEN sc M 3/5 series and positioned so that
the muting lamp is clearly visible form the whole danger zone.
}
Use a muting lamp with an LED lamp and a max. current consumption of 250 mA.
}
If the muting lamp is defective, the muting function cannot be activated. Any attempt to
activate the function will immediately trigger the PSEN sc M 3/5 series and instantly
switch off the OSSDs; the muting lamp fault indicator will also light.
4.11

Override

With the override function, a machine can be restarted even though the safety zone is viol-
ated by material.
The aim is to clear the danger zone of any material that may have accumulated due to a
fault in the operating cycle.
If there is a pallet in the safety zone, for example, and the conveyor can no longer be
switched on because the safety laser scanner is keeping the OSSDs switched off (because
the safety zone is not free), the accumulated material cannot be transported away from the
zone.
Activating the override function allows intervention and enables the conveyor to be restar-
ted.
The safety laser scanner has two connections for override, which are connected via N/O
contacts at 24 VDC (Override 1) and 0 VDC (Override 2). Both contacts are closed if the
override function is activated.
Automatic ending of override function
The override function is ended automatically when one of the following conditions is met:
}
Muting timeout has elapsed
}
The conditions necessary for activation are no longer present.
}
Max. duration of override function has elapsed: After 120 s, the safety laser scanner
switches back to its normal operating status.
}
No muting sensor is active
}
Safety zone is not violated
4.12

Stationary danger zone

Using the safety laser scanner, you can monitor a stationary danger zone, e.g. the environ-
ment of a machine that is installed in a fixed position.
The monitored area can be divided into subsections, for which monitoring can be activated
and deactivated each.
Operating Manual PSEN sc M 3/5 series