Slave Unit - Pilz PSEN sc M 3 Series Operating Manual

Table of Contents

Advertisement

Wiring
}
M12 12-pin male connector for connection to an evaluation device and the supply voltage
– An OSSD pair
– One configurable input
– Four configurable inputs/outputs
– Two inputs for supply voltage
– Functional earth
Pin/colour
1
4
2
6
3
7
9
10
11
8
5
12
}
M12 8-pin socket, hinged
– Connection to the slave unit
}
M12 4-pin socket, hinged
Connection of the safety laser scanner to the configuration PC
The configurable inputs and outputs can be used for both input signals and output signals.
The configurable inputs can be used for all input signals.
}
Restart and reset
}
EDM (when using the 12-pin connection)
}
Switching the monitoring of zone sets
}
Dynamic and static muting
6.2.2

Slave unit

The slave unit of the safety laser scanners PSEN sc M 3/5 series has two 8-pin M12 sock-
ets for connecting to the master unit or to a different slave unit. In PSENscan Configurator
this configuration also has to be made when creating a new configuration.
}
Two hinged 8-pin M12 sockets for connecting to a master unit or a slave unit
– Two inputs at the socket to the master or at an upstream slave unit
– Two outputs at the socket to the master or at an upstream slave unit
– Two connections each for the supply voltage by the master unit and the functional
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
Brown
24 V DC
Green
24 V DC
Blue
0 V DC
Yellow
0 V DC
White
Configurable input
Black
Configurable input/output
Red
Configurable input/output
Purple
Configurable input/output
Grey/pink
Configurable input/output
Grey
OSSD 1
Pink
OSSD 2
Red/blue
Functional earth
earth
Description
| 50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Psen sc m 5 series6d0000166d0000176d0000206d000021Psen sc m 3.0 08-12 ... Show all

Table of Contents