Troubleshooting
Error
Output
A warning or alarm
Depends on configuration
is pending.
When "fully flooded" is
selected in "Tank
BD
Properties" (002), the
measured value jumps
during draining
operations
When "Partially Filled"
is selected in "Tank
Properties" (002), the
BD
measured value jumps
during filling operations
Slope error in interface
measured value
70
9.3

Application errors

F m/ft
actual
expected
E m/ft
F m/ft
expected
actual
E m/ft
F m/ft
actual
expected
E m/ft
Levelflex M FMP40 with HART/4...20 mA
Possible cause
See table of error
messages
(→ ä 68)
The total level is
detected outside the
"Upper Block Distance"
(059).
t →
The total level runs
into the set "Upper
Block Distance" (059).
t →
Wrong DK value set in
"Medium Properties"
(003)
t →
Remedial action
See table of error messages
(→ ä 68)
Yes
1. Increase "Upper Block Dist." (059)
2. "Partially Filled" setting in
"Tank Properties" (002)
Yes
Reduce "Upper Block Dist." (059)
Yes
Check the DK value setting in
"Medium Properties" (003).