Installation
wall
94
pipe
!
26
Installation with remote electronics
• When installing, please observe the instructions on → ä 20.
• Mount housing on a wall or pipe (vertically or horizontally) as shown in the diagram.
65
78
ENDRESS+HAUSER
Levelflex M
85
52
65
78
ENDRESS+HAUSER
Levelflex M
85
52
94
Note!
The protective hose cannot be disassembled at these points (1).
The ambient temperature for the connecting pipe (2) between the probe and the electronics must
not exceed 105°C.
For the remote electronics, temperatures up to 280 °C or 400 °C (depending on the device version)
are admissible at the process connection.
The version with remote electronics consists of the probe, a connecting cable and the housing.
If they are ordered as a complete unit they are assembled when delivered.
88
4 x Ø 8,5
Levelflex M FMP40 with HART/4...20 mA
1
1
2
Note min.
bend radius!
1
1
Ø 76
L00-FMP4xxxx-17-00-00-en-015