Run time measurement
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP40
Run Time Measurement
9
BA244F/00/en/03.09
No. 71074798
Valid as of software version:
01.04.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex M FMP40

  • Page 1 Operating Instructions Levelflex M FMP40 Run Time Measurement BA244F/00/en/03.09 No. 71074798 Valid as of software version: 01.04.zz...
  • Page 2 Commissioning via Endress+Hauser operating program In the "Commissioning" section, you learn how to switch on the device and check the functioning. Additional information on the operation via the Endress+Hauser operating program (FieldCare) can be found in Operating Instructions BA027S/04. Æ...
  • Page 3 Levelflex M FMP40 with FOUNDATION Fieldbus Brief overview Brief operating instructions Levelflex M - Brief operating instructions KA189F/00/a2/03.07 52012501 Contrast: measured value dist./ meas value Group selection basic setup tank medium process empty full dist./ check range of start properties property cond.
  • Page 4 Brief overview Levelflex M FMP40 with FOUNDATION Fieldbus Endress + Hauser...
  • Page 5: Table Of Contents

    Software history ......101 Contact addresses of Endress+Hauser ..101 Operation .
  • Page 6: Safety Instructions

    Levelflex M FMP40 with FOUNDATION Fieldbus Safety instructions Designated use The Levelflex M FMP40 is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry. Installation, commissioning and operation The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards.
  • Page 7: Notes On Safety Conventions And Symbols

    Levelflex M FMP40 with FOUNDATION Fieldbus Safety instructions Notes on safety conventions and symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
  • Page 8: Identification

    Dat./Insp.: D01301-A Reference to additional safety-relevant documentation L00-FMP4xxxx-18-00-00-en-001 Fig. 1: Information on the nameplate of the Levelflex M FMP40 (example) 2.1.2 Ordering structure This overview does not mark options which are mutually exclusive. Approval: A Non-hazardous area Non-hazardous area, WHG...
  • Page 9 Levelflex M FMP40 with FOUNDATION Fieldbus Identification Probe: A Rope 4mm / 1/6", mainly liquid Rope 6mm / 1/4", solid H Rope 6mm / 1/4", PA > steel, solid, T = 100°C / 212°F Rod 6mm, liquid Rod 12mm, liquid...
  • Page 10 Identification Levelflex M FMP40 with FOUNDATION Fieldbus Process Connection: DN100 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527) DN150 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C) DN150 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527) DN200 PN16 B1, 316L flange EN1092-1 (DIN2527 C) Thread ISO228 G3/4, 316L...
  • Page 11 Levelflex M FMP40 with FOUNDATION Fieldbus Identification Housing; Cable Entry: T12 Alu, coated IP68; plug 7/8" + OVP F23 316L IP68; gland M20 F23 316L IP68; thread G1/2 F23 316L IP68; thread NPT1/2 F23 316L IP66; plug M12 F23 316L IP68; plug 7/8"...
  • Page 12: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 13: Mounting

    Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Mounting Quick installation guide Mounting with threaded boss F12/F23 or T12 housing The housing can be turned 350° in order to simplify access to the display and the terminal compartment 1½" F12/F23 housing...
  • Page 14: Incoming Acceptance, Transport, Storage

    Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Incoming acceptance, transport, storage 3.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 15: Installation Conditions

    Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Installation conditions 3.3.1 Dimensions Housing dimensions Dimensions for the process connection and the probe type → ä 16. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing (Aluminium) L00-T12xxxx-06-00-00-en-001 max. 94...
  • Page 16 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Levelflex M FMP40 - process connection, probe type Housing dimensions → ä 15 F12 / T12 / F23 housing Variant “2”: Variant “3”: Separator remote electronic 4 x Ø 8.5 Ø 60.3 Variant “4”: remote electronic Ø...
  • Page 17: Installation

    Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Installation 3.4.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • For the mounting of threaded connection: 60 mm Open-end spanner for 1½", 50 mm Open-end spanner for ¾".
  • Page 18 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus 3.4.3 Mounting probes in an empty silo " Caution! If there is a risk of electrostatic discharge from the product, then both processconnection and rope must be earthed before the probe is lowered into the silo.
  • Page 19 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting 3.4.4 Mounting rope probes in a partially full silo It is not always possible to empty a silo which is already in operation. Because the probe can be turned in the threaded boss, it can also be mounted when the silo is only partially filled. In order to...
  • Page 20 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus 3.4.5 Engineering hints for level measurement in bulk solids and fluids • Normally, rope probes should be used for bulk solids, rod probes are only suitable for short measuring ranges up to approx. 2 m in bulk solids. This applies above all to applications in which the probe is installed laterally at an angle and for light and pourable bulk solids.
  • Page 21 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Other installations • Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) > is 300 mm over the entire length of the probe, also during operation. • Probe must within the measuring span not touch any internals during operation.
  • Page 22 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Type of probe installation • Probes are mounted to the process connection with threaded connections or flanges and are usually also secured with these. If during this installation there is the danger that the probe end moves so much that it touches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down.
  • Page 23 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Supporting probes against warping For WHG or Ex approval: For probe lengths ≥ 3 m a support is required (see figure). For GL/ABS approval: Rod probes ∅ 16 mm ≤ 1 m permissible, Rod probes ∅ 6 mm not permissible.
  • Page 24 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus 3.4.6 Special notes for bulk solids • In the case of bulk solids, as great a distance as possible from the filling curtain is especially important to avoid wear. • In concrete silos, a large distance (B) should be observed between the probe and the concrete wall, if possible >= 1m, but at least...
  • Page 25 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting 3.4.7 Installation in bulk solid silos Tensile load Bulk solids exert tensile forces on rope probes whose height increases with: • the length of the probe, i.e. max. cover, • the bulk density of the product, •...
  • Page 26 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Since the tensile forces are also heavily dependent on the viscosity of the product, a higher safety factor is necessary for highly viscous products and if there is a risk of cornice build-up.
  • Page 27 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Installation in underground tanks • Use coax probe for nozzles with large diameters in order to avoid reflections at the nozzle wall. L00-FMP4xxxx-17-00-00-yy-022 Measurement in corrosive fluids For measurement in corrosive liquids use Levelflex M FMP41C. When using plastic tanks it is also possible to mount the probe on the outside of the tank (see Installation instructions on →...
  • Page 28 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Mounting Location • Recommended distance B wall-mounted rope probe: ~1/6...1/4 of the container diameter (min. 100 mm/4", concrete silos: min. 500 mm). • Not central (2) in metallic tanks. • Not in the filling curtain (3).
  • Page 29 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting 3.4.9 Notes on special installation situations Welding the probe into the vessel " Caution! Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is not possible, the electronics as well as the HF module must be disconnected. Otherwise the electronics may be damaged.
  • Page 30 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Installation from the side • If installation from above is not possible, the Levelflex can also be mounted from the side. • In this case, always fix the rope probe (see "Fixing rope probe").
  • Page 31 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting • It is also possible to mount the probe externally on the tank wall for measuring in Aqueous solutions. Measurement then takes place through the tank wall without contacting the medium. If people are in the vicinity of the probe mounting location, a plastic half pipe with a diameter of approx.
  • Page 32 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Installation in ≥ DN 300 nozzles If installation in ≥ 300mm/12" nozzles is unavoidable, installation must be carried out in accordance with the sketch on the right. pipe Ø 150 … 180 lower edge of...
  • Page 33 Levelflex M FMP40 with FOUNDATION Fieldbus Mounting 3.4.10 Installation for difficult to access process connections For tight spaces or temperatures above that in the graphic, the electronics housing can be ordered with distance pipe or connecting cable (seperate housing). Installation with distance pipe Follow installation instructions on →...
  • Page 34 Mounting Levelflex M FMP40 with FOUNDATION Fieldbus Installation with remote electronic • Follow installation instructions on → ä 20 • Mount housing on a wall or pipe as shown in the diagram. wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5...
  • Page 35: Post-Installation Check

    Levelflex M FMP40 with FOUNDATION Fieldbus Mounting 3.4.11 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 36: Wiring

    Wiring Levelflex M FMP40 with FOUNDATION Fieldbus Wiring Quick wiring guide Wiring in F12/F23 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the FOUNDATION Fieldbus Caution!
  • Page 37 Levelflex M FMP40 with FOUNDATION Fieldbus Wiring Wiring in T12 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M FOUNDATION...
  • Page 38 Wiring Levelflex M FMP40 with FOUNDATION Fieldbus Wiring with FOUNDATION Fieldbus connector " Before connection please note the following: ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Foundation Fieldbus devices are marked on the Order Code: Ser.-No.: IP68 / NEMA 6P nameplate (1).
  • Page 39: Connecting The Measuring Unit

    Levelflex M FMP40 with FOUNDATION Fieldbus Wiring Connecting the measuring unit Ground connection It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in order to achieve EMC security. Cable gland...
  • Page 40: Recommended Connection

    Wiring Levelflex M FMP40 with FOUNDATION Fieldbus Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to DIN EN 60079-14, standard for testprocedures DIN IEC 60060-1 (10 kA, Puls 8/20 μs) it has to be ensured that •...
  • Page 41: Operation

    •Chap. 5.1 Quick operation guide •Chap. 5.2 Operation with the display and operating module VU331 •Chap. 5.3 Operation with an Endress+Hauser operating program •Chap. 5.4 Operation with a FOUNDATION Fieldbus configuration program •Chap. 5.5 Operation with the handheld terminal Field Communicator 375/FC375...
  • Page 42 Operation Levelflex M FMP40 with FOUNDATION Fieldbus 5.1.1 On-site operation Options for on-site operation •Display and operating module VU331 •Endress+Hauser operating software ("FieldCare") Parameter access by on-site operation The following parameters can be accessed by on-site operation: •Parameters of the instrument specific blocks (Sensor Block, Diagnostic Block, Display Block) •Endress+Hauser service parameters...
  • Page 43: Operation With The Display And Operating Module Vu331

    Levelflex M FMP40 with FOUNDATION Fieldbus Operation Operation with the display and operating module VU331 The LCD module VU 331 for display and operation is located beneath the housing cover. The measured value is legible through the glass in the cover. Open the cover to operate the instrument.
  • Page 44 Operation Levelflex M FMP40 with FOUNDATION Fieldbus 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning.
  • Page 45 Levelflex M FMP40 with FOUNDATION Fieldbus Operation 5.2.4 The operating menu Function codes For easy orientation within the function menus, for each function a position is shown on the display. L00-FMRxxxxx-07-00-00-de-005 The first two digits identify the function group: •basic setup •safety settings...
  • Page 46 Operation Levelflex M FMP40 with FOUNDATION Fieldbus Navigation within the menu ENDRESS + HAUSER – >3 s Return to basic setup medium property tank shape Group Selection safety settings Standard aluminium tank length calibr. plastic tank bypass / pipe linearisation...
  • Page 47: Operation With An Endress+Hauser Operating Program

    Operation with an Endress+Hauser operating program 5.3.1 FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser instruments as well as instruments from other manufacturers that support the FDT standard. The following operating systems are supported: Win2000, Windows XP and Windows Vista.
  • Page 48 Operation Levelflex M FMP40 with FOUNDATION Fieldbus Menu-guided commissioning L00-FMP4xxxx-20-00-00-en-001 Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Endress + Hauser...
  • Page 49 Levelflex M FMP40 with FOUNDATION Fieldbus Operation Tank linearisation L00-fmp-Ixxx-20-00-00-en-041 Endress + Hauser...
  • Page 50: Operation With A Foundation Fieldbus Configuration Program

    Operation Levelflex M FMP40 with FOUNDATION Fieldbus Operation with a FOUNDATION Fieldbus configuration program 5.4.1 FOUNDATION Fieldbus configuration programs The user can obtain special configuration and operating programs offered by different manufacturers for use in configuration. These can be used for configuring both the FOUNDATION Fieldbus functions and all the instrument-specific parameters.
  • Page 51: Operation With The Handheld Terminal Field Communicator 375/Fc375

    A FOUNDATION Fieldbus configuration tool offers two types of parameter representation: •Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" •Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Operation with the handheld terminal Field Communicator 375/FC375 5.5.1...
  • Page 52 Operation Levelflex M FMP40 with FOUNDATION Fieldbus 5.5.4 Example basic setup dsdmdm df das. asdas fa asas la. tank properties: standard Fieldbus Live Device List Number of Devices found = 1 standard Address aluminium tank plastic tank E+H_LEVELFLEX_M_XXXXXXX bypass / pipe...
  • Page 53: Commissioning

    • Chap. 6.6 "Blocking distance" • Chap. 6.7 "Envelope curve" • Chap. 6.8 "Basic setup with the Endress+Hauser operating program" • Chap. 6.9 "Commissioning with a FOUNDATION Fieldbus configuration tool" • Chap. 6.10 "Commissioning with the handheld terminal Field Communicator 375/FC375"...
  • Page 54 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus 6.2.2 Key combination (display and operating module VU331) Locking Press S, O and F simultaneously. Unlocking If you try to change a parameter, the following appears: L00-fmrxf0a4-20-00-00-de-001 Press S, O and F simultaneously. The "unlock parameter" (0A4) function appears.
  • Page 55: Resetting The Instrument

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Resetting the instrument It is advisable to reset the instrument parameters before the commissioning if you want to use a instrument with an unknown history. 6.3.1 Resetting the parameters of the FOUNDATION Fieldbus...
  • Page 56 – "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
  • Page 57: Basic Setup

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Basic setup tank shape flange: Standard reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. mapping E = empty calibr. (= zero) LN = probe length setting in 005...
  • Page 58 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus The Levelflex is precalibrated at the factory to the probe length ordered so that in most cases only the application parameters, which automatically adapt the instrument to the measuring conditions, need the entered. For models with a current output, the factory calibration for zero point and span F is 4 mA and 20 mA, for digital outputs and the display module 0 % and 100 %.
  • Page 59: Commissioning By The Display And Operating Module Vu331

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Commissioning by the display and operating module VU331 6.5.1 Power up instrument When the instrument is switched on for the first time, the following messages appear in a sequence of 5 s on the display: software version, communication protocoll and language selection ⇒...
  • Page 60 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus 6.5.2 Function group "basic setup" (00) ⇒ ENDRESS + HAUSER – Function "tank properties" (002) ⇒ ENDRESS + HAUSER – This function is used to select the tank properties. Selection: • standard • aluminium tank •...
  • Page 61 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning concrete wall The "concrete wall" option takes into account the signal-damping property of concrete walls when mounting with < 1 m distance to the wall. Function "medium property" (003) ⇒ ENDRESS + HAUSER –...
  • Page 62 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Function "process propert" (004) ⇒ ENDRESS + HAUSER – Use this funtcion to adapt the instrument to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard •...
  • Page 63 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length.
  • Page 64 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Function "determine length" (034) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be determined automatically. Due to the mounting conditions, the automatically determined probe length may be larger than the actual probe ( typically 20 ...
  • Page 65 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (=span). 100% F = full calibration (= span) F max = E –...
  • Page 66 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Function "check distance" (051) ⇒ ENDRESS + HAUSER – This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available: Options: •...
  • Page 67 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Distance = ok Use this function for partially covered probes. Choose "manual" or "probe free" if the probe is free. • Mapping is carried out up to the currently measured echo • The range to be suppressed is suggested in the "range of mapping" (052) function It is wise to carry out a mapping even in this instance.
  • Page 68 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Function "dist./meas.value" (008) ⇒ ENDRESS + HAUSER – The distance measured from the reference point to the product surface and the measured value calculated with the aid of the empty calibration are displayed again. Check whether the values correspond to the actual meas.
  • Page 69: Blocking Distance

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is set to 0.2 m at the factory.
  • Page 70 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Maximum measured error Typical statements for reference conditions: DIN EN 61298-2, percentage of the span. Output: Digital Analogue sum of non-linearity, measurig range: ± 0.06 % non-repeatability – up to 10 m: ±3 mm and hysteresis –...
  • Page 71: Envelope Curve

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Envelope curve After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended. 6.7.1 Funxtion "plot settings" (0E1) In this function, select whether you want to display •...
  • Page 72 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Check that the following conditions are fulfilled: • The echo quality at the end of measuring range should be at least 10dB. • There should be practically no interference echoes in front of the level signal.
  • Page 73 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning 6.7.8 Navigation in the envelope curve display Using navigation, the envelope curve can be scaled horizontally and vertically and shifted to the left or the right. The active navigation mode is indicated by a symbol in the top left hand corner of the display.
  • Page 74: Basic Setup With The Endress+Hauser Operating Program

    Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Exiting the navigation • Press again to run through the different modes of the envelope curve navigation. • Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve"...
  • Page 75 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Basic setup step 2/6: • Enter the application parameters (see chapter basic setup with "VU331"): – tank properties – medium properties – process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
  • Page 76 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Basic setup step 4/6: • Enter the application parameters (see chapter basic setup with "VU331"): – probe length – probe – probe length – determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
  • Page 77 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Basic setup step 6/6: • Interference echo suppression takes place in this step • The measured distance and the current measured value are always displayed in the header l00-fmp4xxxx-20-00-00-en-006.gif 6.8.1 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve.
  • Page 78 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Evaluating the measurement with the aid of the envelope curve Typical curve shapes: The following examples display typical curve shapes for a rope or rod probe in an empty tank. For all probe types, a negative probe end signal is shown. For rope probes, the end weight causes an additional preliminary positive echo (see rope probe diagram).
  • Page 79 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning Evaluating the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.
  • Page 80: Commissioning With A Foundation Fieldbus Configuration Tool

    Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning with a FOUNDATION Fieldbus configuration tool Note! For commissioning of the instrument with a FOUNDATION Fieldbus configuration tool you need to know the INSTRUMENT_ID, which consists of the following parts: Instrument_ID = 452B481012-XXXXXXXX...
  • Page 81 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning 6.9.2 Parametrization of the Resource Block (Start Index: 400) Enter the desired block name (optional). Factory setting: RESOURCE_XXXXXXXX Opern the Resource Block On delivery, write protection is disabled so that you can access the write parameters via FOUNDATION Fieldbus.
  • Page 82 – by the display and operating module VU331 (see section 6.4.5) – by an Endress+Hauser operating program (see section 6.5.1) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
  • Page 83 Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning 6.9.4 Parametrization of the Analog Input Blocks Levelflex M has two Analog Input Blocks that can be assigned to the various process variables. The following descripiton provides an example for the Analog Input Block 1 (Start Index 500).
  • Page 84 Commissioning Levelflex M FMP40 with FOUNDATION Fieldbus In addition to the limit values you must also specify the action taken if a limit value is exceeded using the alarm priorities (parameters HI_HI_PRI, HI_PRI, LO_PRI, LO_LO_PRI). Reporting to the the fieldbus host system only takes place if the alarm priority is higher than 2. For details refer to section 11.7 in the Appendix.
  • Page 85: Commissioning With The Handheld Terminal Field Communicator 375/Fc375

    Levelflex M FMP40 with FOUNDATION Fieldbus Commissioning 6.10 Commissioning with the handheld terminal Field Communicator 375/FC375 The steps of the commissioning procedure are the same as with a FOUNDATION Fieldbus configuration tool (→ Chap. 6.9). The blocks should be parametrized in the following order: •...
  • Page 86: Maintenance

    Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves (see Chap. 9.4 "Spare Parts" → ä 99). Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 87: Accessories

    Levelflex M FMP40 with FOUNDATION Fieldbus Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001).
  • Page 88: Remote Display And Operation Fhx40

    Accessories Levelflex M FMP40 with FOUNDATION Fieldbus Remote display and operation FHX40 Micropilot M Wall-mounting Pipe-mounting Levelflex M (without mounting bracket) (mounting bracket and plate Prosonic M e r . e r . supplied optionally, s. product structure) o . : o .
  • Page 89: Centering Disks

    Levelflex M FMP40 with FOUNDATION Fieldbus Accessories Centering disks If the probes with rod version are used in stilling well or bypass, it must be ensured that the probe does not come into contact with the wall. The centering disk fixes the rod probe in the middle of the pipe.
  • Page 90: Commubox Fxa291

    Levelflex M FMP40 with FOUNDATION Fieldbus Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291"...
  • Page 91: Adapter Flange Fau70E / Fau70A

    Levelflex M FMP40 with FOUNDATION Fieldbus Accessories Adapter flange FAU70E / FAU70A adapter flange probe nozzle L00-FMP4xxxx-00-00-00-en-001 Process Connection 12 DN50 PN16 A, flange EN1092-1 (DIN2527 B) 14 DN80 PN16 A, flange EN1092-1 (DIN2527 B) 15 DN100 PN16 A, flange EN1092-1 (DIN2527 B)
  • Page 92: Extension Rod / Centering

    Accessories Levelflex M FMP40 with FOUNDATION Fieldbus Extension rod / Centering DN 50 (2") DN 80 (3") DN 150 (6") DN 200 (8") DN 250 (10") nozzle For DN200 and DN250 height in combination with horn adapter Keep metal tube...
  • Page 93: Isolated Tie Down

    Levelflex M FMP40 with FOUNDATION Fieldbus Accessories Isolated tie down Mounting-kit Order - No. Reliable, isolated mounting for 4mm rope probe 52014249 for 6mm rope probe 52014250 If a rope probe has to be fixed and asecure grounded mounting is not possible, we recommend using the insulating...
  • Page 94: Trouble-Shooting

    Trouble-shooting Levelflex M FMP40 with FOUNDATION Fieldbus Trouble-shooting Trouble-shooting instructions Levelflex M -Trouble Shooting Check voltage and Not ok Instrument does compare it with the Connect the Instrument works? Ready specifications on the not respond correct voltage nameplate. Check the polarity...
  • Page 95: System Error Messages

    Levelflex M FMP40 with FOUNDATION Fieldbus Trouble-shooting System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before data reset general reset & new calibr. could be stored; avoid emc problem; required emc problem;...
  • Page 96 Trouble-shooting Levelflex M FMP40 with FOUNDATION Fieldbus Code Description Possible cause Remedy W601 linearisation ch1 curve not linearization not monotonously increasing correct linearisation table monotone W611 less than 2 linearisation number of entered linearization points < 2 correct linearisation table...
  • Page 97: Application Errors

    Levelflex M FMP40 with FOUNDATION Fieldbus Trouble-shooting Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages (→ ä 95 ) has occurred. error messages (→ ä 95) →...
  • Page 98 Trouble-shooting Levelflex M FMP40 with FOUNDATION Fieldbus Device displays a Incorrect probe length 1. Carry out automatic probe length level when the detection when the tank is tank is empty. 100% empty. 2. Carry out mapping over entire probe when the tank is empty (probe free!).
  • Page 99: Spare Parts

    Levelflex M FMP40 with FOUNDATION Fieldbus Trouble-shooting Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows: Go to "www.endress.com" and select your country.
  • Page 100: Return

    Levelflex M FMP40 with FOUNDATION Fieldbus Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 101: Software History

    ---- ---- 10.2008 01.04.04 Function "LAS" improved BA244F/00/en/03.09 ---- 71074798 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress + Hauser...
  • Page 102: Technical Data

    Technical data Levelflex M FMP40 with FOUNDATION Fieldbus Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between a reference point (see Fig. on → ä 16) and the Measured variable product surface. Subject to the input empty distance (E, see Fig. on → ä 116), the level is calculated.
  • Page 103 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data Source VCRs Sink VCRs Subscriber VCRs Publisher VCRs Link Settings Slot time Min. Inter PDU delay Max. response delay Transducer Blocks Block Content Output values Sensor Block contains all parameters related to the measurement •...
  • Page 104 Technical data Levelflex M FMP40 with FOUNDATION Fieldbus Block Content Execution time Functionality Integrator Block The Integrator Function Block integrates a variable as a 60 ms standard function of the time or accumulates the counts from a Pulse Input block. The block may be used as a totalizer...
  • Page 105 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data 10.1.4 Performance characteristics Reference operating • temperature = +20 °C (68 °F) ±5 °C (9 °F) conditions • pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi) • humidity = 65 % ±20% •...
  • Page 106 Technical data Levelflex M FMP40 with FOUNDATION Fieldbus 10.1.5 Operating conditions: Environment Ambient temperature range Ambient temperature for the transmitter: -40 °C ... +80 °C (-40 °F … +176 °F) The functionality of the LCD display may be limited for temperatures Ta<-20 °C and Ta>+60 °C.
  • Page 107 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data 10.1.6 Operating conditions: Process Process temperature range The maximum permitted temperature at the process connection (see Figure for measuring point) is determined by the O-ring version ordered: O-ring-material min. Temperature max. Temperature FKM (Viton) -30 °C/-22 °F...
  • Page 108 All Probes with ¾"- connection Lower edge of the process connections: PPS-GF 40 Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L with the material number 1.4435 or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13E0 in EN1092-1 Tab.18.
  • Page 109 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data 10.1.7 Mechanical construction Tolerance of probe length Rod probes over 1 m / 3.2 ft 3 m / 9.8 ft 6 m / 20 ft up to 1 m / 3.2 ft 3 m / 9.8 ft...
  • Page 110 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. WHG. See "Ordering structure" on → ä 8 - (see ZE 256F/de).
  • Page 111 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data Assignment of the certificates (XA, ZD, ZE) to the device: Feature Non-hazardous area NEPSI Ex em(ia) IIC T6 Non-hazardous area, WHG ATEX II 3G Ex nA II T6 NEPSI Ex ia IIC T6...
  • Page 112 Technical data Levelflex M FMP40 with FOUNDATION Fieldbus 10.1.9 Additional documentation Note! This Additional documentation can be found on our product pages on www.endress.com. • Technical Information (TI358F/00/en) • Safety Manual "Functional safety manual" (SD174F/00/en) • Certificate "Allgemeine bauaufsichtliche Zulassung" (ZE256F/00/de)
  • Page 113 Levelflex M FMP40 with FOUNDATION Fieldbus Technical data Endress + Hauser...
  • Page 114: Appendix

    Appendix Levelflex M FMP40 with FOUNDATION Fieldbus Appendix 11.1 Operating menu FOUNDATION Fieldbus basic setup tank properties medium cond. process proper. end of probe 030 determine length empty calibr. enter value standard unknown standard see Function group “leghth adjustment 03”...
  • Page 115 Levelflex M FMP40 with FOUNDATION Fieldbus Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed probe free dist.
  • Page 116: Description Of Functions

    Appendix Levelflex M FMP40 with FOUNDATION Fieldbus 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA245F – "Description of the instrument functions" on the enclosed CD-ROM. 11.3 Function and system design 11.3.1...
  • Page 117 • with a Personal Computer, FXA291 and ToF Adapter FXA291 (USB) and the operating software "FieldCare". The FieldCare is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 118: Index

    Levelflex M FMP40 with FOUNDATION Fieldbus Index Index Abgleich leer ........64 Nameplate .
  • Page 119 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 120 www.endress.com/worldwide BA244F/00/en/03.09 No. 71074798 CCS/FM+SGML 6.0/ProMoDo 71074798...