Installation
18
3.4.1
Electronics
The process variables are output using the dynamic variables of the HART protocol. The process
variables can be flexibly assigned to the dynamic variables (primary, secondary, tertiary, quaternary
value).
Dynamic variables of the
Possible process variable assignment
HART protocol
Primary value (PV)
• Interface (default)
• Total level
• Thickness of the upper medium (upper phase)
Secondary value (SV)
• Total level (default)
• Interface
• Thickness of the upper medium (upper phase)
Tertiary value (TV)
• Thickness of the upper medium
(upper phase) (default)
• Interface
• Total level
• Amplitude of the total level signal
th
Quaternary (4
) value (QV) Amplitude of the interface level signal
3.4.2
Using the HART loop converter HMX50:
The dynamic variables of the HART protocol can be converted into individual 4 to 20 mA sections
using the HART loop converter HMX50. The variables are assigned to the current output and the
measuring ranges to the individual parameters in the HMX50.
Levelflex M
HART
Power
Fig. 2:
Connection diagram for HART loop converter HMX50 (example: passive 2-wire device and current outputs
connected as power source)
The HART loop converter HMX50 can be acquired using the order number 71063562.
Additional documentation: TI429F and BA371F.
Levelflex M FMP40 with HART/4...20 mA
Eingang
Eingang
Relais 1
Relay 1
Input
1
+
+
2
-
3
Relais 2
Relais 2
Relay 2
4
5
6
Stromausgang 1
Current output 1
Stromausgang 2
Current output 2
Power
versorgung
supply
Current output 3
Stromausgang 3
22 23 24
24V DC
Comment
The "primary value" is permanently
assigned to the 4 to 20mA current
output
No variable assignment
10
HART Loop Converter HMX50
11
12
16
17
18
7
8
9
13
14
15
19
20
Commubox
FXA191/195
21
HART
L00-FMP40xIx-04-00-00-en-004