Endress+Hauser Levelflex M FMP40 Operating Instructions Manual page 76

Run time measurement
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

Technical data
Cleaning the probe
Electromagnetic compatibility
(EMC)
Process temperature range
!
76
Depending on the application, contamination or buildup can accumulate on the probe. A thin, even
layer only has a slight impact on the measurement. Thick layers can dampen the signal and then
reduce the measuring range. Severe, uneven buildup, adhesion e.g. through crystallization, can lead
to incorrect measurement. In such instances, we recommend you use a non-contact measuring
principle, or check the probe regularly for fouling.
Electromagnetic compatibility to EN 61326 and NAMUR Recommendation EMC (NE21). Details
are provided in the Declaration of Conformity.
A standard installation cable is sufficient if only the analog signal is used. Use a shielded cable when
working with a superimposed communication signal (HART).
When installing the probes in metal and concrete tanks and when using a coax probe:
• Interference emission to EN 61326 - x series, Class A equipment.
• Interference immunity to EN 61326 - x series, requirements for industrial areas and NAMUR
Recommendation NE 21 (EMC)
The measured value can be affected by strong electromagnetic fields when installing rod probes
without a shielding/metal wall, e.g. plastic, and in wooden silos.
• Interference emission to EN 61326 - x series, Class A equipment.
• Interference immunity: the measured value can be affected by strong electromagnetic fields.
10.1.5
Operating conditions: process
The maximum permitted temperature at the process connection (see Figure for measuring point) is
determined by the O-ring version ordered:
O-ring material
Min. temperature
FKM (Viton)
EPDM
FFKM (Kalrez)
1)
For PA-coated probes, the maximal admissible temperature is 100 °C.
2)
The min. temperature of FFKM can be -15 °C if the max. temperature of +80 °C is not exceeded.
Note!
The medium temperature can be higher.
The metal uninsulated probes are only insulated in the area of the bushing. Thus, there is no danger
of electrostatic charging.
Levelflex M FMP40 with HART/4...20 mA
Max. temperature
-30 °C
+150 °C
-40 °C
+120 °C
2)
-5 °C
+150 °C
1)
measured
here
Endress+Hauser