Run time measurement
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

Levelflex M FMP40 with HART/4...20 mA
The measured values
for the interface and the
total level are identical
If the interface layers
are thin, the total level
jumps to the interface
level
Interface measured
value jumps
Endress+Hauser
F m/ft
expected
actual
E m/ft
F m/ft
expected
actual
E m/ft
F m/ft
actual
actual
expected
expected
E m/ft
Echo threshold for the
total level too high
t →
The thickness of the
upper phase is less than
60 mm.
t →
Emulsion layer present
t →
Troubleshooting
Yes
Check the DK value setting in
"Medium Properties" (003).
Yes
Interface measurement is only possible
if the thickness of the interface is
greater than 60 mm.
Yes
Emulsion layer affects the measurement.
Please contact Endress+Hauser.
71