Endress+Hauser Levelflex M FMP40 Operating Instructions Manual page 31

Run time measurement
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

Levelflex M FMP40 with HART/4...20 mA
Endress+Hauser
Cable entry
Cable gland: M20x1.5 (only cable entry for Ex d)
Cable entry: G ½ or ½ NPT
Supply voltage
HART, 2-wire
All the following values are the terminal voltages directly at the device:
Communication
HART
Fixed current, adjustable e.g. for
solar power operation (measured
value transmitted via HART)
Fixed current for HART Multidrop
mode
1)
Startup current 11 mA.
HART residual ripple, 2-wire: U
Power consumption
Min. 60 mW, max. 900 mW
Current consumption
Communication
HART, 2-wire
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the use
of overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1
(10 kA, pulse 8/20 μs), the following applies:
• The measuring device is used with integrated overvoltage protection with 600V gas tube surge
arrester in the T12 housing, refer to product overview on → ä 8
or
• This protection is achieved by the use of other appropriate measures (external protection devices
e.g. HAW262Z).
Current consumption
4 mA
Standard
20 mA
4 mA
Ex ia
20 mA
4 mA
Ex em
Ex d
20 mA
Standard
11 mA
Ex ia
11 mA
1)
Standard
4 mA
1)
Ex ia
4 mA
≤ 200 mV
ss
Output current
Current consumption/power consumption
3.6 to 22 mA
Wiring
Terminal voltage
Minimum
Maximum
16 V
36 V
7.5 V
36 V
16 V
30 V
7.5 V
30 V
16 V
30 V
11 V
30 V
10 V
36 V
10 V
30 V
16 V
36 V
16 V
30 V
31